How To Configure "3-Wire" Control With Run/Stop; Pushbuttons And Forward/Reverse Selection - Mitsubishi Electric D700-SC Easy Start Manual

Table of Contents

Advertisement

Easy Start Guide
Mitsubishi D700-SC Series Inverter

12. How to configure "3-Wire" control with Run/Stop

pushbuttons and Forward/Reverse selection

The procedure described in section 7 enables
Run/Stop operation via the red and green
buttons on the Inverter keypad.
If this is unsuitable for the application, remote
switches can be used instead.
12.1 Parameters to change for remote 3-wire control
Parameter Description
Pr. 2
Minimum Speed
Pr. 160
Extended function display
Pr. 180
RL terminal function selection
Pr. 250
Stop selection
1 2
Pushbutton
Normally Open
Normally Closed
"Run"
This guide has been produced by The Inverter Drive Supermarket Ltd.
All content, including but not limited to graphics, text and procedures copyright
Drive Supermarket and must not be reproduced or altered without prior written permission.
How to set
Set to
5.00
Set to
0
to display both simple and extended parameters. This is the factory default.
Default is 0. Set to
Default is 9999. Set to
1
3
2 4
1 3
Pushbutton
Switch, 2 Position
Normally Open
"Stop"
"Forward / Reverse"
This section explains how to enable 3-wire
control with Run and Stop via pushbuttons and
Fwd/Rev via a selector switch.
The Inverter must be in "EXT" control mode to
operate from the I/O terminals. Press PU/EXT
to select.
to run the motor at 5Hz if no other speed reference has been defined.
25
to set the RL terminal as "Output Stop".
8888
for Run with Forward/Reverse selection.
12.2 Connecting the Switches
The PC terminal is a common connection for
terminals RL, RM, RH, STF and STR when the
jumpers are set in "Source" (the default). If the
jumpers have been changed to "Sink", use SD as
the common instead.
For "Run" and "Stop", two suitable pushbuttons
should be installed. The "Run" pushbutton should
include a Normally Open contact between
terminals RL and STF and the "Stop" a Normally
Closed contact between RL and PC.
For "Forward/Reverse" a suitable 2 position NO
(Normally Open) switch should be installed
between RL and STR. A momentary connection
between RL and STF will start the motor. It will
continue to run until the connection between RL
and PC is broken.
1 4
Note that the Forward/Reverse switch can only be
used to set the direction when the motor is stopped.
It will not change the direction once the motor is
R
running. If this is not suitable, an alternate 3-wire
configuration with Run Forward, Run Reverse and
Stop is possible - refer to the manual for details.
The Inverter must be in external control mode to
operate in 3-wire control. Check that the "EXT"
indicator is illuminated to confirm. The PU/EXT key
can be used to change the mode if required.
©
The Inverter
Page 12