DISASSEMBLY PROCEDURE-Drain pan

8-6. Drain pan

Procedures
1. Remove the cap from the service panel 3 , and check the
drain pan for water.
Drain water from the drain port if there is any.
*Protect the surroundings with a plastic sheet before
draining water.
2. Removing the drain pan (Figure 6-1)
(1) Remove the 12 mounting screws from base plate A.
(2) Pull down the drain pan. Loosening the mounting screw
on base plate B will make it easy to remove base plate A.
*Pull out the drain pan by pulling a little in all directions.
Drain pan is made of styrofoam. Handle the drain pan
carefully so as not to break it.
HWE1212A
Explanatory figure
Base plate B
Base plate A
Figure 6-1
23
Drain pan