3.8.

Securing the Cabinet

Once the cabinet has been correctly located, it must be secured into place by
lowering the cabinet feet to prevent the cabinet from rolling.
D009
D009:
When fully equipped, a cabinet is extremely heavy and must be secured
into place before use or maintenance.
Incorrect installation may result in serious personal injury or damage to
components.
D038
D038:
Do not move the rack cabinet when the feet are lowered.
Required Tools
• 1 tape measure
• 1 bubble level
• 2 open-end wrenches (size 17 mm)
Procedure
1. Using the 2 x 17mm open-end wrenches, raise the cabinet 11 centimeters
off the floor by lowering all 6 cabinet feet.
2. Using the bubble level, check that the cabinet is stable and secure.
3. Tighten all 6 feet counter-nuts firmly against the cabinet base.