Dell S5000 Series Installation And Service Manual page 93

Servers for sap hana
Hide thumbs Also See for S5000 Series:
Table of Contents

Advertisement

5.5.
Installing a PDU
Each PDU is delivered with mounting brackets for vertical and/or horizontal
installation in the cabinet.
Note Vertical Installation
Important Before choosing a location for a PDU, check power cable
Required Tools
• Hex wrench
• PDU fixtures
Procedure: Horizontal Installation
1. Select the required location in the cabinet.
2. Install 2 cage nuts (A) over the required rack fixture holes on each side of
the cabinet.
3. Align the PDU fixture holes with the rack fixture holes on the left and right
sides of the cabinet.
4. Insert the bolt and washer assemblies in the top and bottom PDU fixture
holes (B) and tighten with the hex wrench.
Up to six PDUs can be installed vertically in the cabinet flange space (3
right and 3 left).
length from the servers and devices you want to connect to
the PDU.
Before proceeding to install the PDU, check that the circuit
breaker switch is OFF.
Chapter 5.
Servicing the Rack Cabinet
5-17