2.3.3.
Environmental Conditions for Water-Cooled Cabinets
Important Consult your air-conditioning system specialist for advice
For a cooling capacity of up to 40 KW, the following environmental conditions
must be complied with:
Room temperature 20°C:
Room temperature 25°C:
Waterflow:
Pressure drop:
Important You are strongly advised to contact the support team for
on how to plan for the installation of water-cooled
cabinets.
12°C
2 liters per second
140 kPa typical at 2l/second
expert advice on how to optimize cooling.
Chapter 2.
Input water temperature 7°C
Input water temperature