Electrical Field Connections - Briggs & Stratton 040661 Installation And Operation Manual

Single phase air-cooled standby generator system 17 kw/20 kw/26 kw
Table of Contents

Advertisement

Installation
B. For NG, rotate the lever clockwise 90° so the
handle position of the lever will be up and down
and the "NG" letters (D) will be on the left.
D
Figure 12
10. Find the fuel selector switch (E) in the engine
compartment. See Figure 13.
11. Select either LP or NG.
E
Figure 13
12. Connect the negative (-) cable at the battery.
13. Install the end cap controller end.
14. Install the 15-amp fuse.
15. Push and hold the config button on the controller to
access the configuration menu.
16. Push the select button to edit the items in the
configuration menu.
17. To set up the generator's controller for LP fuel,
enter the configuration menu by using the dealer
password, which is available on the Power Portal.
Part No. 80106286
Revision C
18. Navigate to "select profile" and press "select" on the
correct profile for the generator. For example, choose
"20KW_LP" for operating a 20 kW unit running on
LP fuel.
Note: Selecting a profile that is not intended for the
generator can cause the generator to run erratically and
could result in damage.
19. To save the new fuel setting, press and hold the stop/
config button until "Saving Settings..." displays.
20. For additional information on the operation of
the generator controller, refer to the Operation
Instructions GC1030 SERIES GENSET Controller
Manual, part number 80086364.
21. Push the controller auto button.
22. Restore utility power to the generator.
23. Close the roof.

Electrical Field Connections

WARNING
cause electrical shock or burns, resulting in death or
serious injury.
• A licensed professional must perform the
installation.
• Disconnect all sources of electricity before
installing or servicing equipment.
• Ground the system before applying power.
WARNING
Installing low- and high-voltage wire in the same
conduit could cause electric shock or burns, resulting
in death or serious injury.
• Do not run low- and high-voltage wire in the same
conduit unless the insulation rating on ALL wiring is
rated for 600V. See NFPA 70 for more information.
Low-voltage connections occur via a field connections
terminal block (E) in the main electrical area. Compare
the following illustration with your generator to get
familiar with the location of these connections.
23
Electrical Field Connections
Generator voltage could
Hazardous Voltage –

Hide quick links:

Advertisement

Chapters

Table of Contents
loading

Table of Contents