ABB SLT900 Operating Instructions Manual page 23

Submersible level transmitter for water/waste and the process industry
Table of Contents

Advertisement

Använd:
• DOX9, se Konfigurera transmitter på sida 14.
• HART handterminal.
---------------------------------------------------------------------------------------------------------------
Fel:
Utsignalen varierar kraftigt
Orsak:
Processtrycket kan vara påverkat av turbulens, gasbubblor
eller liknande.
Åtgärd:
Kontrollera processen.
Ändra transmitterns tidskonstant (dämpning) till ett högre
värde.
---------------------------------------------------------------------------------------------------------------
6.2
Felaktigt mätvärde
---------------------------------------------------------------------------------------------------------------
Fel:
Transmittern visar felaktiga mätvärden.
Orsak:
Transmitterns fabrikskalibrering kan ha ändrats p g a yttre
påverkan eller åldrande.
Åtgärd:
Med DOX9 utför Underhållskalibrering.
---------------------------------------------------------------------------------------------------------------
Fel:
Vid Looptest (fast utställd ström 4 mA eller 20 mA) avviker
värdet med mer än ±0,003 mA.
Orsak:
Utsignalen kan ha påverkats av yttre omständighet.
Åtgärd:
Med DOX9 utför Utsignalskalibrering.
---------------------------------------------------------------------------------------------------------------
Fel:
Tryckvärdet visar inte 0 när inget tryck är pålagt på membranet.
Orsak:
Mätsondens läge kan ha ändrats, t ex från vertikalt till
horisontalt. Membranet kan ha utsatts för mekanisk
deformation, åldrande eller liknande.
Åtgärd:
Med DOX9 utför Autozero.
---------------------------------------------------------------------------------------------------------------
Fel:
Tryckvärdet för 4 mA och 20 mA inställda med en trycknormal
avviker något när de avläses med DOX9.
Orsak:
Transmitterns läge kan ha ändrats, t ex från vertikalt till
horisontalt. Membranet kan ha utsatts för mekanisk
deformation, åldrande eller liknande.
Åtgärd:
De via HART-kommunikationen avlästa tryckvärdena beräknas
utifrån transmitterns översättning av trycket på membranet till
önskad enhet, t ex kPa. Översättningen kan avvika något pga att
transmitterns digitala kalibrering kan ha ändrats pga. tex. åldring
eller yttre påverkan.
Utför Underhållskalibrering.
23
• HART hand held terminal.
---------------------------------------------------------------------------------------------------------------
Error:
The change in output value is to fast.
Cause:
The pressure can be influenced by turbulens, bubbles
or the like.
Measure:
Check the process.
Change the damping value to a higher value.
---------------------------------------------------------------------------------------------------------------
6.2
Wrong output value
---------------------------------------------------------------------------------------------------------------
Error:
The output value is wrong (as known).
Cause:
The transmitters factory calibration can have been changed due
to damage or aging.
Measure:
Perform a Maintenance Calibration with DOX9.
---------------------------------------------------------------------------------------------------------------
Error:
When checking the output current with Looptest (fixed current 4
mA or 20 mA) a deviation of more than ±0,003 mA is noticed.
Cause:
The output current can have been affected by aging or external
influence.
Measure:
Perform an Output signal calibration with DOX9.
---------------------------------------------------------------------------------------------------------------
Error:
The pressure output value (read by HART) differs from zero
when the pressure on the diaphragm is zero.
Orsak:
The measuring probes position can have been changed , for
example from vertical to horisontal. The diaphragm may have
been affected by dirt, deformation, aging or similar.
Measure:
Perform an Autozero with DOX9.
---------------------------------------------------------------------------------------------------------------
Error:
The pressure output values for 4 mA and 20 mA calibrated with a
high precision pressure regulator shows a deviation when read
with DOX9 or a hand held terminal (read by HART).
Cause:
The measuring probes position may have been changed, for
example from vertical to horisontal. The diaphragm can have
been affected by dirt, deformation, aging or similar.
Measure:
The output values red by HART-communicationen are
calculated from the pressure on the diaphragm to for example
kPa. The calculation can shift slightly due to changes in the
transmitters digital calibration, aging or external influence.
Perform an Output signal calibration with DOX9.