ABB AC 800M Manual page 84

Controller hardware
Hide thumbs Also See for AC 800M:
Table of Contents

Advertisement

Installing the PM86x/TP830 Processor Unit in Single Configuration
Communication Ports
CN1 and CN2
The control network connects to one or two RJ45 connectors (CN1 and CN2)
depending on network option (single or redundant).
Use an RJ45 connector for IEEE802.3 (Ethernet) for connecting to a category 5
Shielded Twisted Pair cable (STP class 5).
Class 5, or higher, cable 10/100BaseT/TX max 100 m (110 yd). ABB recommends
the use of optical fiber in an industrial environment, for example 62.5/125
100BaseFX, max. distance 1500 m (1600 yd).
Housing
PM851/PM851A is restricted to one Ethernet (CN1) port, thus redundant
Ethernet is not available.
84
Table 5. TP830 CN1 and CN2 Connections (RJ45 connectors)
Pin
Designation
1
TD+
2
TD-
3
RD+
4–5
6
RD-
7–8
Shield
Direction
Out
Transmit Data (plus)
Out
Transmit Data (minus)
In
Receive Data (plus)
Not used
In
Receive Data (minus)
Not used
Shield
Section 2 Installation
Description
3BSE036351-510 A