Prefabricated aluminum profile
CI869 AF 100 Interface
CI872 MOD5 Interface
CI871 PROFINET IO Interface
CI873 EtherNet/IP DeviceNet
Interface
BC810 CEX-Bus
Interconnection Unit
SM810
SM811
S800 I/O Units
(1) The key positions are common to CI867, CI868, CI871 and CI873. Hence caution must be
exercised in field replacement. Ensure that correct CI is inserted, especially in hot insert.
For further details on pre-set Alpha codes, refer to the relevant unit documentation.
Ensure that the baseplate and the unit to be mounted have compatible Alpha codes.
Otherwise it may result in equipment damage. Any difficulty in installing a unit on a
particular baseplate indicates a difference in Alpha Code lock.
See
Figure 24
The mechanical keys are delivered pre-set and must not be altered. This prevents the
removable interface being placed on the wrong type of baseplate.
Do not manipulate the locking device. ABB will take no responsibility for
errors caused by manipulating locking devices.
76
Table 4. Factory Pre-set Alpha Codes (Continued)
Unit
Various – see S800 I/O
Product/User's Guide
on page 77 for further details of the Alpha code lock arrangement.
Key Position 1
D
D
(1)
D
(1)
D
C
C
D
Section 2 Installation
Key Position 2
C
E
(1)
B
(1)
B
A
B
D
Various – see S800 I/O
Product/User's Guide
3BSE036351-510 A