ABB AC 800M Manual page 112

Controller hardware
Hide thumbs Also See for AC 800M:
Table of Contents

Advertisement

Installing the PROFIBUS DP Interface, CI851/TP851
Installation of PROFIBUS DP
For installation of the fieldbus and recommended certified fieldbus devices and
components, see fieldbus documentation and
Components. The PROFIBUS DP must be connected with shielded twisted pair
cables.
For additional information on PROFIBUS DP and other suitable components,
visit the PROFIBUS User Organization web site.
Note that there is no unit redundancy for the CI851 unit.
Cannot be used in High Integrity Controller.
CI851 has been replaced by the CI854 communication interface. CI851 is only
described for legacy reasons.
It is not possible to change the CI851 unit via hot swap and it is not allowed to
perform an online upgrade of firmware in a system containing CI851.
112
Table 12. CI851 - PROFIBUS DP Connector
PIN
Designation
1
2
3
4
RTS(TTL) Indicates direction RTS(TTL) Indicates direction
5
GND Bus
6
+5 V Bus
7
8
9
Shield
Shield/protective ground
Not Used
B-line
Receive/Transmit Data B-line
GND Bus
For terminating resistors
Not used
A-line
Receive/Transmit Data A-line
Not used
Appendix C, Recommended
Section 2 Installation
Description
3BSE036351-510 A