Gaggenau AH 590-120 Original Operating And Assembly Instructions page 13

Freely suspended insular hood
Hide thumbs Also See for AH 590-120:
Table of Contents

Advertisement

6. Assembly instructions
6.1 Technical data
Weight without support frame and LK:
AH 590: 35 kg
AH 592: 33 kg
Weight with support frame and LK:
max. 60 kg
Dimensions: 1198 x 700 mm
Electrical connection
Pay attention to the rating plate data.
The mains connecting cable must at least
correspond to the type H 05 VV-F G 0,75.
The appliance must only be connected by an
authorised specialist. The specialist is respon-
sible for perfect functioning of the appliance at its
installation location. He must explain the operating
principle of the appliance to the user with reference
to the operating instructions. He must explain to the
user how the appliance can be disconnected from
the mains whenever required.
Connection possibilities
The plug of the connecting cable is inserted into
the socket on the ceiling. If this is not possible, the
disconnection of all the poles of the appliance from
the mains must be achieved by way of the domestic
fuse, or by using an accessible disconnecting device
with a contact gap of at least 3 mm.
12
6.2 Installation
The applicable regulations of the energy supply
companies and the regional construction regula-
tions must be observed when installing the hood.
The minimum distance from the worktop to the
bottom edge of the hood is for electrical appliances
600 mm and for gas appliances 700 mm.
The extractor hood was conceived for the exhaust
air mode. The exhaust air can be routed into a se-
parate exhaust air shaft or directly into the open
through the outside wall.
It is not allowed to pass the exhaust air into a flue
or exhaust air chimney that is in operation or into a
shaft that is linked to the heating basement. Consult
the chimney sweep responsible for your district
whenever you wish to pass the exhaust air into a
chimney that is not in operation.
During the course of planning, a chimney sweep
must be consulted if a room air-dependent hearth
is operated in the same room as the one in which a
hood is operated in the exhaust air mode. Adequate
incoming air must be ensured. The applicable con-
struction and safety regulations must be observed.
Adequate incoming air must be ensured if a wood,
coal, gas or oil heater or an open hearth is operated
in the same room as the one in which the hood is in-
stalled.
Safe operation is possible whenever the partial va-
cuum in the place where the firing equipment
is installed does not exceed 4 Pa (0.04 mbar).
This can be achieved whenever the air needed for
combustion is able to enter through openings that
cannot be sealed, for example in doors, windows,
incoming/exhaust air wall boxes or by other techni-
cal means.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ah 592-120

Table of Contents