F341
Light-Load Frequency for Automatic High-Speed Operation
(Crane/Hoist)
Program ⇒ Special Control Parameters ⇒ Crane/Hoist Load
This parameter establishes the speed that the ASD will ramp to when operating
in the Light-Load/High-Speed mode.
On-Trip Powerline Switching
Program ⇒ Terminal Selection Parameters ⇒ Line Power Switching
This parameter Enables/Disables the On Trip Powerline Switching feature.
When enabled, the system is instructed to discontinue using the output of the
drive and to switch to the commercial power in the event of a trip.
At-Frequency Powerline Switching
Program ⇒ Terminal Selection Parameters ⇒ Line Power Switching
When enabled, this parameter sets the frequency at which the At Frequency
Powerline Switching function engages. The At Frequency Powerline
Switching function commands the system to discontinue using the output of the
drive and to switch to commercial power once reaching the frequency set here.
ASD-side Switching Wait Time
Program ⇒ Terminal Selection Parameters ⇒ Line Power Switching
This parameter determines the amount of time that the drive will wait before
outputting a signal to the motor once the switch-to-drive-output criteria has
been met.
112
Direct Access Number — F341
Parameter Type — Numerical
Factory Default — 80.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 80.0
Units — Hz
Direct Access Number — F354
Parameter Type — Check Box
Factory Default — Disabled
Changeable During Run — No
Direct Access Number — F355
Parameter Type — Numerical
Factory Default — 60.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 80.0
Units — Hz
Direct Access Number — F356
Parameter Type — Numerical
Factory Default — 0.67
Changeable During Run — Yes
Minimum — 0.01
Maximum — 10.0
Units — Seconds
G7 ASD Operation Manual
F356