Download Print this page

Baso C107U Quick Reference Manual page 8

Advertisement

FLAME CURRENT MEASUREMENT
Flame current of the device can be measured using a standard
microammeter by simply touching the meter leads to the 2 PIN labeled FC,
as shown in Figure 2.
• Flame current must be measured with flame lit and main gas
flowing
• Set meter to DC μAmp scale.
• Make sure meter leads are positioned correctly [+/-].
• Typical Flame Sense Current of 0.4 to 1.0 μAmp DC
BLACK (-)
Important: Preventative maintenance programs are an important part of maintaining
optimum and safe function of you BASO Products. Any attempt to repair this assembly
voids the manufacturer's 2-year warranty. For a replacement control, contact the original
equipment manufacturer or nearest BASO Gas Products distributer.
450 East Horseshoe Road
PO Box 170
Watertown, WI 53094
1-877-227-6427 (1-877-BASOGAS)
©
2019 BASO Gas Products
Part No. BASO-INS-C107UQRG, Rev. C
RED (+)
Figure 2: Microammeter Connection.
24 VAC Universa Direct Spark Gas Ignition Control
.
www.baso.com
Published in U.S.A.
www.baso.com
8