4.
Purge the lines before attaching them to the fuel manifold.
5.
Adjust the pressure relief valve until the required oil pressure is attained.
6.
See the individual burner performance sheets for approximate valve settings. (See Burner
Performance Data Sheets for proper fuel flows.)
7.
Final pump pressure will have to be adjusted to obtain the rated burner output, depending on system
design.
8.
High fire oil flow can be set by adjusting fuel pressure or by restroking the oil valve. Refer to individual
burner performance sheets. (See Burner Performance Data Sheets)
9.
The manual low fire bypass oil control valve is used to set and maintain the low fire oil flow at the
burner. Refer to individual burner performance sheets. (See Burner Performance Data Sheets)
10.
The low oil pressure switch is factory set at 30 PSIG.
11.
The high oil pressure switch is factory set at 150 PSIG.
WARNING!
Final settings will have to be adjusted for the particular operating conditions.
Be sure not to have more fuel flow than there is combustion air available, or "puffing" and a
dangerously rich firing condition could occur.