Cisco Nexus 7010 Chassis Clearances

The Cisco Nexus 7010 chassis requires the following clearances (see
the Cisco Nexus 7010 Switch, on page
• Front clearance of 45.5 inches (115.6 cm) for both of the following:
Note
• Rear clearance of 35 inches (88.9 cm) for both of the following:
Air intake from cold aisle for power supplies
Air intake from cold aisle for the supervisor,
fabric, and I/O modules
Air exhaust to hot aisle for the power supplies
Air exhaust to hot aisle for the supervisor, fabric,
and I/O modules
• Cabling area of 7.5 inches (19.1 cm) between the front of the chassis and the inside of the cabinet
or front of the rack
• Maintenance area of 38 inches (96.5 cm) of cold-aisle passageway in front of the rack or cabinet
You might need to increase the maintenance area to accommodate a wide mechanical lift used to move the
chassis to or from the rack.
• Airflow area of 5 inches (12.7 cm) inside of the cabinet or rack
• Maintenance area of 30 inches (76.2 cm) of hot-aisle passageway behind the rack or cabinet
13
Airflow clearance required between the chassis
and inside of cabinet (if used)
14
Chassis depth
15
Clearance required between the front of the
chassis and the front of the cable management
frames and the optional front doors
16
Front service clearance required for installing
the chassis and replacing the modules
198):
Cisco Nexus 7000 Series Hardware Installation and Reference Guide
Cisco Nexus 7010 Chassis Clearances
Figure 138: Clearances Required for
197