Two stage set point control, ranges 0 - 30, 0 - 100, and 0 - 200 psi
Table of Contents

Advertisement

Set Point 1
• Set Point 1 controls when Output 1 is energized or open as
shown in the Example.
• When Output 1 is energized, the Black output wires will be
continuous.
• When Output 1 is open, the Black output wires will be
open.
• To adjust Set Point 1, use the following steps:
1. Digi-Span should be displaying sensor pressure.
2. Press the center button and release it. The display will
change to show SP1. Wait 2 seconds or press the UP
or DOWN button and the set point will be displayed.
3. Press and hold either the UP or DOWN button until the
desired set point is displayed.
NOTE: Set Point 1 can not be set below Set Point 2. If
pressing the DOWN button does not lower Set Point 1,
it may be necessary to lower Set Point 2 (see below).
4. Wait approximately 10 seconds. If the set point was
changed, the display will flash. Then the Digi-Span will
return to displaying the sensor pressure. (If you don’t
want to wait 10 seconds, press the center button once
for Set Point 2, twice for Differential, three times for
Offset or four times to display sensor pressure.)
Set Point 2
• Set Point 2 controls when Output 2 is energized or open as
shown in the Example.
• When Output 2 is energized, the Red output wires will be
continuous.
• When Output 2 is open, the Red output wires will be open.
• To adjust Set Point 2, use the following steps:
1. Digi-Span should be displaying sensor pressure.
2. Press the center button twice and release it. The
display will change to show SP2. Wait 2 seconds or
press the UP or DOWN button and the set point will be
displayed.
3. Press and hold either the UP or DOWN button until the
desired set point is displayed.
NOTE: Set Point 2 can not be set above Set Point 1. If
pressing the UP button does not increase Set Point 2, it
may be necessary to raise Set Point 1 (see above).
4. Wait approximately 10 seconds. If the set point was
changed, the display will flash. Then the Digi-Span will
return to displaying the sensor pressure. (If you don’t
want to wait 10 seconds, press the center button once
for Differential, twice for Offset, or three times to display
sensor pressure.)
COC OPERATION
4
SET POINT and DIFFERENTIAL EXAMPLE
Set Point 1
Set Point 2
Differential
OUTPUT 1 - BLACK
On a rise to 60psi Stage 1 will Energize
Light will Flash
--------------------------------------------------
On a drop to 58psi Stage 1 will Open
Light is OFF
OUTPUT 2 - RED
On a drop to 38psi Stage 2 will Energize
Light is ON
--------------------------------------------------
On a rise to 40psi Stage 2 will Open
Light is OFF
60psi
40psi
2psi