Connecting Loads
Loads can be connected to the generator by the Output
Terminal Lugs, convenience receptacles, or optional
camlocks (Figure 17). Make sure to read the operation
manual before attempting to connect a load to the generator.
To protect the output terminals from overload, a 3-pole,
1000-amp, main circuit breaker is provided. Make sure to
switch ALL circuit breakers to the OFF position prior to
starting the engine.
HARD WIRE
HOOKUP PANEL
BLACK
RED
BLUE
WHITE
GREEN
O
U
V
W
GROUND
LOAD
NEUTRAL
Figure 17. Connecting Loads
PAGE 32 — DCA400SSI4F/DCA400SSI4F3 60 HZ GENERATOR • OPERATION MANUAL — REV. #3 (04/18/22)
OUTPUT TERMINAL PANEL FAMILIARIZATION
CS-6369
TWIST-LOCK
RECEPTACLES
LOAD
GFCI
RECEPTACLES
LOAD
CAMLOCKS (OPTION)
Overcurrent Relay
An overcurrent relay (Figure 18) is connected to the
main circuit breaker. In the event of an overload, both the
circuit breaker and the overcurrent relay may trip. If the
circuit breaker cannot be reset, the reset button on the
overcurrent relay must be pressed. The overcurrent relay
is located inside the control box.
Figure 18. Overcurrent Relay
NOTICE
Remember the overcurrent relay monitors the current
flowing from the U,V, and W Output Terminal Lugs
to the load.
In the event of a short circuit or overcurrent condition,
it will automatically trip the 1000-amp main breaker.
To restore power to the Output Terminal Panel, press
the reset button on the overcurrent relay and place the
main circuit breaker in the closed position (ON).