Generator Shut-Down Procedures - MULTIQUIP Power WHISPERWATT DCA70USI2 Operation And Parts Manual

Whisperwatt series 60hz generator
Table of Contents

Advertisement

13. Place the main, gFCI, and aux. circuit breakers in the
on position (Figure 51).
Figure 51. Main, Aux. and GFCI
Circuit Breakers (ON)
14. Observe the generator's ammeter (Figure 52) and
verify it reads the anticipated amount of current with
respect to the load. The ammeter will only display a
current reading if a load is in use.
Figure 52. Ammeter (Load)
15. The generator will run until manually stopped or an
abnormal condition occurs.
WarnIng
never stop the engine suddenly except in an
emergency.
normal ShUTDoWn proCeDUre
To shutdown the generator, use the following procedure:
1. Place both the maIn, gFCI and loaD circuit breakers
as shown in Figure 53 to the oFF position.
Figure 53. Main, GFCI and Load
Circuit Breakers (OFF
page 36 — DCa70USI2 60 hz generaTor • operaTIon anD parTS manUal — rev. #0 (06/28/11)

generatOr shut-dOWn prOcedures

2. Place the engine speed switch (Figure 54) in the "loW"
3. Let the engine cool by running it at low speed for 3-5
4. Place the mpeC Control Switch (Figure 55) to the
5. Verify that all status LEDs on the MPEC display are
6. Remove all loads from the generator.
7. Inspect entire generator for any damage or loosening of
emergenCY ShUTDoWn proCeDUre
1. Place the mpeC Control Switch (Figure 55) in the
aUTomaTIC ShUT-DoWn SYSTem
This unit is equipped with safety devices to automatically
stop the engine in the event of low oil pressure, approximately
14 psi (97 kPa), or high water temperature, approximately
230° F (110° C), overspeed approximately +15%. The alarm
lamps on the ECU illuminate to signify the reason for the
shutdown.
(down) position..
Figure 54. Engine Speed Switch (Low)
minutes with no load applied.
oFF/reSeT position.
Figure 55. MPEC Control Switch (Off/Reset)
oFF (not lit).
components that may have occurred during operation.
oFF/reSeT position.
NOTICE
Before inspecting generator, check that the Auto/
Manual switch is in the oFF/reSeT position, and place
all circuit breakers in the oFF position. Allow sufficient
time for adequate cooling. When ready to restart,
complete all steps in the Generator Startup Procedure
section of this manual.