NEBS Regulatory Compliance Statements

NEBS Regulatory Compliance Statements
The NEBS-GR-1089-CORE regulatory compliance statements and requirements are discussed in this section.
Warning
The intra-building port(s) (Management Ethernet Ports) of the equipment or subassembly must use
shielded intra-building cabling/wiring that is grounded at both ends. Statement 7003
Warning
The intra-building port(s) (Management Ethernet Ports) of the equipment or subassembly is suitable
for connection to intra-building or unexposed wiring or cabling only. The intra-building port(s) of the
equipment or subassembly must not be metallically connected to interfaces that connect to the OSP or
its wiring for more than 6 meters (approximately 20 feet). These interfaces are designed for use as
intra-building interfaces only (Type 2, 4, or 4a ports as described in GR-1089) and require isolation
from the exposed OSP cabling. The addition of Primary Protectors is not sufficient protection in order
to connect these interfaces metallically to an OSP wiring system. Statement 7005
Products that have AC power ports that are intended for deployments where an external Surge Protective
Device (SPD) is utilized at the AC power service equipment (see definition in National Electric Code).
Statement 7012
This product is designed for a Common Bonding Network (CBN) installation. Statement 7013
This product can be installed in network telecommunication facilities or locations where the National
Electric Code applies. Statement 8015 and 8016
The DC return connection to this system should remain isolated from the system frame and chassis
(DC-I). Statement 7016
Safety Guidelines
6
Safety Guidelines