2.2 Contents of the mounting and installation
instructions
Any person authorised to carry out work on or with the
equipment must have read and understood the operating
instructions before commencing work on the equipment.
This also applies if the person concerned has worked with
the same or similar equipment in the past or was trained by
the manufacturer.
2.3 Changes and alterations to the equip-
ment
In order to avoid hazards and to ensure the best possible
performance, no modifications, retrofits and add-ons are
permitted on the equipment unless these were expressly
approved by the manufacturer.

2.4 Responsibility of the operating entity

These operating instructions must be kept in the direct
vicinity of the equipment and must always be accessible to
people working on or with the equipment. The equipment
must only be operated if it is in an exemplary and operationally
safe condition. The equipment must be checked every time
before it is put into operation. The operating instructions as
set out in the manual must be complied with in full!

3 Technical Data

Tabelle 1: Technical Data
DualGuard-S
Typ
ESF30 30P
Approval empty enclosure /
Certificates
DIBT
Empty enclosure
Fire exposure from outside
30
(min)
Enclosure specifications
Enclosure
Fibre plates
Protection rating
IP42
Protection class
l
Dimensions
2115 x 898 x 549
(H x W x D in mm)
Weight (kg) empty cabinet
330
Closure
Sash fastener
Electronic specifications
Rated voltage
400 V 50 Hz
Number of module slots
0-30
Max. conductor size / final
4
circuits (mm²)
Max. conductor size (mm²)
35
Max. total conductor
775
size (mm²)
Mounting and Operating Instructions Fire-Resistant Cabinet Type DualGuard-S ESF30 October 2022 www.eaton.com

2.5 Personnel requirements

Only authorised and qualified personnel may carry out
work on or with the device. These personnel must have
been trained in possible hazards that may occur. A qualified
person is anyone who, based on his/her training, expertise
and experience as well as his/her knowledge of the relevant
provisions, is able to assess the work that he/she has been
given and to identify any potential hazards.

2.6 Work safety

Following the safety information and instructions provided in
this operating manual is essential to avoid bodily injuries and
property damage while working on and with the equipment.
DualGuard-S
DualGuard-S
ESF30 15P
ESF30 SOU5
DIBT
VDE
30
30
Fibre plates
External fibre plates
/ Internal plastic
IP42
IP65
l
l
1265 x 898 x 449
1135 x 396 x 230
187
81
Sash fastener
Sash fastener
230 V 50 Hz
230 V 50 Hz
0-15
5
4
4
35
10
625
89
DualGuard-S
DualGuard-S
ESF30 SOU3
ESF30 SOU2
VDE
VDE
30
30
External fibre plates
External fibre plates
/ Internal plastic
/ Internal plastic
IP65
IP65
l
l
835 x 396 x 230
685 x 396 x 230
61
51
Sash fastener
Sash fastener
230 V 50 Hz
230 V 50 Hz
3
2
4
4
10
10
79
74
2 Safety
DualGuard-S
ESF30 SOU1
VDE
30
External fibre plates
/ Internal plastic
IP65
I
535 x 396 x 230
35
Sash fastener
230 V 50 Hz
1
4
10
39
5