Product certifications

Rev 2.7
European Directive information
A copy of the EU Declaration of Conformity can be found at the end of the
Quick Start Guide. The most recent revision of the EU Declaration of
Conformity can be found at Emerson.com/Rosemount.
Ordinary Location Certification
The Rosemount 214C has been examined and tested to determine that the
design meets the basic electrical, mechanical, and fire protection
requirements by a nationally recognized test laboratory (NRTL) as accredited
by the Federal Occupational Safety and Health Administration (OSHA).
Note
The terminal strip in the Aluminum with Terminal Strip (AT1 or AT3)
connection head requires sensor lead wires to have a wire termination (Ex:
Bootlace ferrule or spade lug).
North America
The US National Electrical Code
(CEC) permit the use of Division marked equipment in Zones and Zone
marked equipment in Divisions. The markings must be suitable for the area
classification, gas, and temperature class. This information is clearly defined
in the respective codes.
6.1
North America
6.1.1
E5 USA Explosionproof (XP) and Dust-Ignitionproof (DIP)
Certificate 70044744
Standards FM 3600:2011, FM 3615:2006, UL 50E:2007, UL
Markings
Special Conditions for Safe Use (X):
1. Flameproof joints are not intended for repair.
2. Cable entries must be used which maintain the ingress protection of
the enclosure. Unused cable entries must be filled with suitable
blanking plugs.
10
®
61010-1:2010, ANSI/ISA 60529:2004
XP CL I, DIV 1, GP B, C, D; DIP CL II, DIV 1, GP E, F, G; CL III; T6
(-50 °C ≤ T
≤ +80 °C), T5 (-50 °C ≤ T
a
required; installed per Rosemount drawing 00214-1030; Type
4X
and IP 66/67; V
(NEC) and the Canadian Electrical Code
≤ +95 °C); Seal not
a
35 VDC, 750 mW
max
May 2021
max
Emerson.com/Rosemount