List Of Applicable No-Fuse Breaker - Savch S900 Series User Manual

Multi function mini type (im)
Table of Contents

Advertisement

Operational Environment
temperature
Storing temperature
Operational Environment dampness
Installation height
Vibration
Protection level
SAVCH ELECTRIC shall not be responsible for faults due to the following:
(1) Absence or inapplicable or over large non-fuse breakers was put between the power supply and the
which results in the inverter fault.
(2) Magnetic contactors or advance capacitor or Surge Absorber were connected in series between the inverter and
motor.
● A three phase squirrel-cage induction motor which corresponds with the capacity of the inverter shall be adopted.
● If more than one motors were driven simultaneously by one inverter, the current of these motors when running shall
below capacity of the inverter. And each motor shall be prepared with a thermal relay in appropriate capacity.
● Phase advance capacitors and other capacity elements such as LC or RC shall not be fixed between the inverter
and motor.

4. LIST OF APPLICABLE NO-FUSE BREAKER

The wire size recommended to main circuit terminals is to use single-stranded HIV wire (max. allowable temperature
75℃) under ambient temperature of 40℃. The content in ( ) is the example of single-stranded IV wire (max.
allowable temperature 60℃).
Type
S900-2S
motor (kW)
single-phase series
S900-2S0.2G
S900-2S0.4G
S900-2S0.75G
S900-2S1.5G
S900-2S2.2G
Type
S900-4T
motor (kW)
three-phase series
S900-4T0.4G
S900-4T0.75G
S900-4T1.5G
S900-4T2.2G
S900-4T3.7G
-10℃ to +50℃ (+40℃ parallel installation, no condensation, no
freezing)
-20℃ to +60℃
Below 90%RH without moister
Lower than 1000m, without corrosive gas, fluid and dust.
Under 20Hz 9.80665m/s
IP20
Suitable
Rated
power of
current of
breaker (A)
0.2
10
0.4
15
0.75
20
1.5
40
2.2
50
Suitable
Rated
power of
current of
breaker (A)
0.4
5
0.75
10
1.5
15
2.2
15
3.7
20
2
(1g), 20 to 50Hz 5.88 m/s
Main circuit (mm
Positive and
Input wire
negative bus
1
1
1.5
1
2.5
1
4
1.5
5.5
1.5
Main circuit (mm
Positive and
Input wire
negative bus
1
1
1
1
1.5
1
1.5
1.5
2.5
1.5
9
2
(0.6g)
2
)
Output
Grounding
wire
wire
1
2
1
2
1
2
2.5
2
2.5
2
2
)
Grounding
Output wire
wire
1
22
1
22
1.5
22
1.5
22
2.5
22
inverter,
Control
2
circuit (mm
)
Control
terminal wire
1
1
1
1
1
Control circuit
2
(mm
)
Control
terminal wire
1
1
1
1
1