Page 1
MULTIPURPOSE UNITS FOR 2/4 - PIPE SYSTEMS - Technical manual NRP 0280-0750 REVERSIBLE HEAT PUMPS • DESIGNED FOR 2 AND 4 PIPE SYSTEMS FOR EXTERNAL INSTALLATION • OUTDOOR UNIT • HIGH EFFICIENCIES INRP160HzTY. 1312. 5806716_03...
Page 2
AERMEC S.p.A AERMEC S.p.A. reserves the right to make any modifications considered necessary to improve its products at any moment and is not obliged to add these modifications to machines that have already been fabricated, delivered or are under construction.
Page 3
AERMEC S.p.A. 37040 Bevilacqua (VR) Italy–Via Roma, 996 Tel. (+39) 0442 633111 Telefax 0442 93730–(+39) 0442 93566 www.aermec.com -sales@aermec.com ......MODEL SERIAL NUMBER DATE DICHIARAZIONE DI CONFORMITÀ DECLARATION OF CONFORMITY Noi, fi rmatari della presente, dichiariamo so o la nostra esclusiva We, the undersigned, hereby declare under our own responsibility that the assembly in responsabilità...
INDEX General warnings ..................4 Pressure drop .....................22 1.1. Preserva on of the documenta on .............4 1.2. Installa on ....................4 Useful sta c pressures 2|4 pipe system .............24 1.3. Warranty .......................4 13.1. Low sta c pressure pumps in cooling mode - system side 230/460V ..24 1.4.
GENERAL WARNINGS 1.3. WARRANTY The appliance warranty does not cover the costs The NRP AERMEC units are constructed according for ladder trucks, scaffolding, or other elevation to the recognised technical standards and safety systems that may become necessary for carrying out regulations.
PRESENTATION 3.2. FOR 4 PIPE SYSTEMS This separates the two hot-cold sections required for 4-pipe systems. The multipurpose 4-pipe units have been made for Multipurpose OUTDOOR units for 2 or 4 pipe COMBINED PRODUCTION applications with 4 pipe terminals, e.g. shopping systems, especially designed for simultaneous If the utility requires simultaneous hot and centres, offices or facilities with large windows...
4.1. DESCRIPTION AND CHOICE OF THE UNIT Field: 1 2 3 Code 4 5 6 7 Size 0280, 0300, 0330, 0350, 0500, 0550, 0600, 0650, 0700, 0750 8 Version High efficiency (not available for sizes 0280÷0350) Silenced high efficiency (data on demand for sizes 0500÷0750) 9 Type of system: 2 pipe system (cooling + DHW heating) 4 pipe system (cooling + heating)
BASIC OPERATING LAYOUT FOR 2 PIPE SYSTEM BASIC OPERATING LAYOUTS FOR 2 PIPE SYSTEM 3.1. COLD WATER PRODUCTION ONLY TO SYSTEM O SYSTEM RETURN O SYSTEM FLOW System side (EVAPORATION) HEAT EXCHANGER Cold water pr DHW side HEAT EXCHANGER Source side (CONDENSATION) HEAT EXCHANGER Heat ex...
Page 9
3.3. 2 CIRCUITS TO PRODUCE HOT WATER ONLY TO DHW O DHW FLOW O DHW RETURN System side Not running HEAT EXCHANGER DHW side (CONDENSATION) HEAT EXCHANGER DHW pr Source side (EVAPORATION) HEAT EXCHANGER Heat exchange with air 3.4. 2 CIRCUITS TO PRODUCE COLD WATER TO SYSTEM AND HOT WATER TO DHW O DHW FLOW O DHW...
3.5. CIRCUIT FOR PRODUCING HOT WATER TO SYSTEM | CIRCUIT FOR PRODUCING HOT WATER TO DHW O DHW FLOW O DHW RETURN O SYSTEM FLOW O SYSTEM RETURN System side (CONDENSATION) DHW side (CONDENSATION) HEAT EXCHANGER Hot water pr HEAT EXCHANGER DHW pr Source side (EVAPORATION)
Page 11
4.2. HOT WATER PRODUCTION ONLY TO SYSTEM O DHW FLOW O DHW RETURN Cooling side Not running EXCHANGER (CONDENSATION) EXCHANGER Hot water pr Source side (EVAPORATION) HEAT EXCHANGER Heat exchange with air 4.3. SIMULTANEOUS HOT AND COLD WATER PRODUCTION TO SYSTEM O SYSTEM FLOW O SYSTEM...
DESCRIPTION DEHYDRATOR FILTER circuit, it signals the work pressure to the control Hermetic-mechanical with cartridges made of board generating a pre-warning in the case of OF COMPONENTS ceramic and hygroscopic material, able to withhold anomalous pressures. 7.1. STRUCTURE impurities and any traces of humidity present in the HIGH PRESSURE TRANSDUCER cooling circuit.
ACCESSORIES 8.1. MECHANICAL ACCESSORIES 8.2. ELECTRIC ACCESSORIES VT ANTI-VIBRATION MOUNTS AER485P1 PGD1 Group of anti-vibration mounts. RS-485 interface for supervising systems with Graphical display, which allows complete MODBUS protocol. management of the unit like the one on board the GP PROTECTION GRIDS machine.
Page 18
3406,1 4931,7 SOUND POWER SOUND PRESSURE Aermec determines sound power values on the Sound pressure in free field, at 10m / 32,8ft distance basis of measurements made in accordance with from the external surface of the unit (in accordance UNI EN ISO 9614-2, as required for Eurovent certi- with UNI EN ISO 3744).
OPERATIONAL LIMITS 10.1. COOLING MODE COOLING MODE The units, in standard configuration, are not suitable for installation in salty environments. For functioning limits, please refer to the diagrams, valid for ∆t 5°C/10°F. In summer mode, the unit can be started with external air 46°C/114,8°F and inlet water 35°C/95°F.
CORRECTIVE FACTORS FOR DATA DIFFERENT THAN NOMINAL IN COOLING MODE 11.1. COOLING CAPACITY AND INPUT POWER Pc: COOLING CAPACITY Pc: COOLING CAPACITY The refrigerating capacity yielded and the input elec- trical capacity in conditions other than rated conditions are obtained by multiplying the rated values (Pc, Pa) by the respective correction coefficients (Cf, Ca).
11.4. HEATING CAPACITY AND INPUT POWER Ph: HEATING CAPACITY Ph: HEATING CAPACITY The heating capacity yielded and the input electrical capacity in conditions other than rated conditions are obtained by multiplying the rated values (Ph, Pa) by the respective correction coefficients (Ch, Ca).
11.7. CORRECTIVE COEFFICIENTS OF RE COVERED HEATING CAPACITY The refrigerating capacity yielded and the input elec- Ph: HEATING CAPACITY trical capacity in conditions other than rated conditions are obtained by multiplying the rated values (Pc, Pa) by the respective correction coefficients (Cf, Ca).
PRESSURE DROP SYSTEM SIDE (EV) PRESSURE DROP COOLING MODE FUNCTIONING (2/4 PIPES) The diagram pressure drop are related to an average water temperature of 10°C/50°F 20,3 Key: 0280-0300 0330 0350 0500 0550-0600 0700 0750 5000 10000 15000 20000 25000 30000 35000 40000 100 110 120 130 140 150 160 170...
Page 24
RECOVERY MODE WITH DHW SIDE 2 PIPES HOT WATER PRODUCTION SYSTEM SIDE 4 PIPES The diagram pressure drop are related to an average water temperature of 43°C/109,4°F Key: 0280 0300 0330 0350-0500 0550 0600 0650 0700 0750 10000 20000 30000 40000 50000 60000...
EXPANSION VESSEL CALIBRATION 14.1. EXPANSION VESSEL CALIBRATION H max (1) = 55 m Standard pre-load pressure value of the expansion vessel is 1,5bar/21,8PSI, whereas volume is 24 litres. Maximum pressure 6bar/87PSI. Calibration of the vessel must be regulated using the maximum level difference (H) of the user (see H = 12.25 m diagram) by using the following formula: p (calibration) [bar] = H [m] / 10.2 + 0.3.
SOUND DATA SOUND POWER: Total sound levels Octave band[Hz] Aermec determines sound power values on the Pressure 1000 2000 4000 8000 basis of measurements made in accordance with Pot. [dB (A)] [dB (A)] UNI EN ISO 9614-2, as required for Eurovent certi-...
CONTROL AND SAFETY PARAMETERS CALIBRATION Default COOLING SET Max. -10°C / 14°F 7°C / 44,6°F Water inlet temperature in cooling mode 20°C / 68°F Default HEATING SET Max. 30°C / 86°F 50°C / 122°F Inlet water temperature in heating functioning mode 55°C / 131°F Default ANTI FREEZE INTERVENTION...
PART LOAD HEATING (AHRI CONDITIONS) Inlet water temperature 40°C / 104°F Outlet water temperature 45°C / 113°F External air temperature 7°C_44.6°F B.S. / 6°C_42.8°F B.U. COOLING (AHRI CONDITIONS) Outlet water temperature 6,7°C / 44,6°F Flow rate 0,043l/s per kW External temperature 35°C / 95°F LEVELS OF POWER COOLING CAPACITY %...
Page 36
- info@aermec.com AERMEC S.p.A. reserves the right to make any modifications considered necessary to improve its products at any moment and is not obliged to add these modifications to machines that have already been fabricated, delivered or are under construction.