Page 1
2 1 . 0 5 – 5 7 2 3 4 1 0 _ 0 1 T r a n s l a t i o n o f O r i g i n a l i n s t r u c t i o n s NRGI User manual CARD PCO5 w w w .
Page 3
All specifications are subject to change without prior notice. Although every effort has been made to ensure accuracy, Aermec shall not be held liable for any errors or...
TABLE OF CONTENTS Digital input monitor (ID13) - (ID14) - (ID15) ......p. 13 1. User interface (PGD1) ...............p. 6 Digital input monitor (ID16) - (ID17) - (ID18) ......p. 13 Start-up procedure ................p. 6 Digital input monitor (NO1) - (NO2) - (NO3) ......p. 13 Function of the PGD1 control panel keys ........p. 6 Digital input monitor (NO4) - (NO5) - (NO6) ......
Page 5
Setting the BMS 1 parameters ............p. 21 Enable change over and on/off by supervisor ......p. 21 Sets the BMS2 parameters ............... p. 21 Enables system on/off from digital input (ID17) ...... p. 21 Setting thermostat regulation ............p. 22 Sets the logic for the setpoint and differential in cooling mode ......................
USER INTERFACE (PGD1) 1.2 FUNCTION OF THE PGD1 CONTROL PANEL KEYS Function of the PGD1 control panel keys: : Displays the list of active alarms and the alarm log : Pressing this key activates navigation between the menus (orange LED on = winter operating mode active);...
Page 7
Menu icons: IN/OUT: This menu contains advanced information about operating the unit; ON/OFF: This menu is used to activate or deactivate the unit; it also provides state information; System: This menu is used to set the operating mode, the setpoints for water production and the time bands to be applied to the system;...
This mask is used to display the unit's general status: This mask is used to display the cooling circuit's general status; if the unit has mul- tiple circuits, each will have a dedicated window: Aermec Fri 08:35 Circuit 1 9.8°C 23.1bar...
— Activation of the branch containing glycol with the display of moving arrows for Master pump status and water circulation; — Power delivered by the free cooling based on that available; Common Outlet: ---°C — Tot: total power as a percentage delivered by the unit. If only free cooling, corre- sponds to the total power delivered by free cooling, if mixed operation the total power is the sum of the power delivered by free cooling and the compressors;...
INPUT/OUTPUT MENU Defrost 3.1 FAN MONITOR This window summarises the state of the fans and the utilised setpoints: Disabled High ext. temperature Speed 100% Times: Liquid T.: 25.1°C Set: 0.0bar Next defrost: Di : 0.0bar The state of defrosting is divided between two rows, the first can have the following 1:Max Speed 0.0bar states:...
3.5 ANALOGUE INPUT MONITOR (U1) - (U2) 3.8 ANALOGUE INPUT MONITOR (U8) - (U9) Inputs pCO5 Inputs pCO5 U8= Liquid temp. 1 U1= Inlet Temp.water 25.2°C evap.: 25.8°C U2= Outlet Temp.water U9= Liquid temp. 2 evap.: 37.8°C 25.1°C U1: shows the heat exchanger inlet water temperature; U8: this value represents the temperature of the liquid on coil 1 U2: this value represents the temperature of the water leaving the heat exchanger;...
3.11 PEC ANALOGUE INPUT MONITOR (T4) - (T5) 3.14 DIGITAL INPUT MONITOR (ID4) - (ID5) - (ID6) Inputs PEC Inputs pCO5 T4= Liquid temp. ID4:Al. phase monitor 25.0°C Closed ID5:Overl.comp1 circ1 T5= Discharge temp. Closed 50.0°C ID6:Overl.comp2 circ1 Closed T4: this value represents the temperature of the liquid; ID4: shows the binary status read from the input of the phase control device, which T5: this value represents the temperature of the discharge gas on compressor 1;...
3.16 DIGITAL INPUT MONITOR (ID10) - (ID11) - (ID12) 3.18 DIGITAL INPUT MONITOR (ID16) - (ID17) - (ID18) Inputs pCO5 Inputs pCO5 ID10:2nd Set enable ID16:Remote Cool/Heat Open Closed ID11: --- ID17:On-O Closed ID12: --- ID18:Abilita multifunz. Closed ID10: this value represents the state of the digital input connected to the secondary ID16: this value represents the state of the digital input connected to the remote setpoint: season change function:...
3.20 DIGITAL INPUT MONITOR (NO4) - (NO5) - (NO6) 3.22 DIGITAL INPUT MONITOR (NO10) - (NO11) - (NO12) Output pCO5 Output pCO5 NO4:Int.res.1/Boiler NO10: --- Open NO5:Integ.resistance 2 NO11: --- Open NO6:Crankcase resist. NO12: --- Closed NO4: this value represents the state of the digital output connected to activation of If the unit is glycol-free or free cooling, the values for output NO12 are: the supplementary heater 1 or boiler: NO12: this value represents the state of the digital output linked to the 3-way free...
3.24 DIGITAL INPUT MONITOR (NO16) - (NO17) - (NO18) 3.27 ANALOGUE OUTPUT MONITOR (Y1) ~ (Y5) Output pCO5 Output pCO5 NO16:Base resistance 2 Y1= DCP1 Open Y2= V3V VPF NO17:Antifreeze Heater Open Y3= ---- NO18:Pump 2 Y4= ---- Open Y5= ---- NO16: this value represents the state of the digital output connected to activation Y1: this value indicates the current value of the analogue output connected to mod- of the heater on base 2:...
ON/OFF MENU 4.1 GENERAL ON/OFF This window makes it possible to view the general state of the system as well as to turn the unit on or off: On/O Unit Plant O General General enable: Display of the general system state: —...
SYSTEM MENU Plant 5.1 SELECTING THE SYSTEM OPERATING MODE This mask is used to display the current unit state, to turn the unit on or off and to Setpoint 2 select the operating mode: Plant 12.0°C O General 40.0°C Switch On: Mode Selection: The secondary working setpoints are: —...
5.6 COPY/PASTE TIME BANDS NB: this mask is only visible if "BY CLOCK" is selected on the page "Se- lecting the system operating mode"; This mask is used to copy and paste the time bands set for a day of the week to another (or to all other days): Plant Timezone...
RECOVERY MENU 6.1 ENABLING RECOVERY WARNING: this mask is available on units with total recovery. This mask is used to display the actual status of the total recovery, and to enable or disable the total recovery: O General Switch On: The mask displays the total recovery status;the available options are: —...
CLOCK MENU 7.1 SETTING SYSTEM DATE AND TIME This mask is used to set the system date and time: Clock Day: MONDAY Time: 16 MARZ 2020 Hour: 16:29 7.2 SETTING THE AUTOMATIC SUMMER/WINTER TIME CHANGE This mask is used to set the automatic change between summer and winter time, it is also possible to define the day the change is made: Clock Automatic change...
INSTALLER MENU Installer 8.1 PASSWORD TO ACCESS THE INSTALLER MENU (0000) This mask is used to enter the password necessary for accessing the installer menu Supervisor: (the password is 0000): Insert password Enable cooling/heating by supervisor 0000 Enable On-O unit by supervisor 8.4 SETS THE BMS2 PARAMETERS This mask is used to set the parameters related to the serial communication dedi-...
— FIXED SETPOINT: the system uses the values set by the user in the windows of Input enable the set menu as the work setpoint (main and secondary setpoints); — CLIMATIC CURVE: the working setpoint is calculated automatically based on the ID17: ON/OFF plant data entered in the climatic curve;...
Differential: this value indicates the differential to apply to the anti-freeze activation Installer threshold; when the water temperature (inlet or outlet) is higher than the threshold value plus the differential, the anti-freeze alarm is deactivated; Setpoint heat Calculation delta: value to subtract from the current setpoint to obtain the an- ti-freeze alarm threshold if glycol water is enabled;...
8.18 MULTI-FUNCTION INPUT CONFIGURATION (U10) Installatore NB: to use this function, close the contact on input ID18; Recupero totale This mask is used to set the function associated with multifunction input U10: Allarme antigelo Installer 3.0°C Multifunction Input Soglia: 1.0°C Di erenziale: Con g.
8.23 CONFIGURATION OF THE SUPPLEMENTARY ELECTRIC Installer HEATERS Multifunction Input This mask is used to set the operation of the supplementary heaters in case of low outside temperatures: Con g. NTC Installer Suppl.electric heaters Minimum temp.: 15.0°C Number: Maximum temp.: 25.0°C Power: Minimum temp.: this value indicates the minimum temperature (NTC signal) to as-...
8.26 COMPRESSOR HOUR COUNTER MONITOR Installer This window displays the data relative to the operating hours of the compressors Master/Slave on the unit: Hour meter Unit: ALONE Circuit 1 Step: 1.0% Compressor 1: 0000h Slave Pump o with Compressor 2: 0000h Compressor o : (Unit: this value indicates the type of setting for the unit;...
This window contains information concerning the unit code, the software version Di erential pressure. and the machine test date: Setpoint: 150mbar Informazioni Di .: 100mbar Aermec S.p.A. Integral: 180s Code: NRGI602XH°A°J°00 Ver.: 0.1.000 16/03/20 Enable: this value indicates whether to activate or deactivate this mode; the pos- sible states are: —...
Installer Language: ENGLISH Push ENTER for change 8.38 CONFIGURATION OF THE UNITS OF MEASURE This window is used to set the units of measure to use in the system: Options Type of measurem.unit STANDARD [°C/bar] Supervisor BMS STANDARD [°C/bar] Type of units of measure: indicates the units of measure shown on the display; the possible states are: —...
LIST OF ALARMS There are three types of alarm resets: — Auto: automatic, when the event causing the alarm stops, also the alarm disappears. — Manual: manual, to restart normal operation manual acknowledgement is necessary. — Semi-auto: semi-automatic, the alarm is automatic but if it is present more than “n” times, it then becomes manual. The interventions are decreased by one unit every hour. Furthermore, there is a “timeout”, after which the alarm becomes manual, even if the maximum number of interventions is reached.
Page 32
SCARICA L’ULTIMA VERSIONE: DOWNLOAD THE LATEST VERSION: TÉLÉCHARGER LA DERNIÈRE VERSION: A E R M E C S . p . A . V i a R o m a , 9 9 6 - 3 7 0 4 0 B e v i l a c q u a ( V R ) - I t a l y P h o n e + 3 9 0 4 4 2 6 3 3 1 1 1 - F a x + 3 9 0 4 4 2 9 3 5 7 7 s a l e s @ a e r m e c .