Electrical Data; Circuits / Unit Only; Circuits - Nordyne Q6SP-090 Series Installation Instructions Manual

Single package electric heat pump rooftop unit
Table of Contents

Advertisement

MODEL
NOMINAL
NUMBER
UNIT
Q6SP-
VOLTAGE
(SEE NOTES 2 & 3)
(SEE NOTE 1)
-090Ca
208 - 230 V
-090Da
460 V
-120Ca
208 - 230 V
-120Da
460 V
-090Ca
208 - 230 V
-090Da
460 V
-090Ca
208 - 230 V
-090Da
460 V
-120Ca
208 - 230 V
-120Da
460 V
Table 2. Q6SP Electrical Data - Multiple Supply Circuits / Unit Only
H5HK
HEATER KIT
NOMINAL
MODEL #
HEATER
(SEE NOTE 6)
KW
009Q-01
9
018Q-11
18
030Q-22
30
035Q-22
35
009S-01
9
018S-01
18
030S-01
30
035S-01
35
NOTES:
1. To achieve the rated unit performance, unit voltage should be within 2% of nominal.
2. For C series units:
Nominal Unit Input Voltage = 208-230 Volt, 60 Hertz, 3 Phase
Minimum allowed unit voltage = 187V
Maximum allowed voltage = 253V
3. For D series units:
Nominal Unit Input Voltage = 460 Volt, 60 Hertz, 3 Phase
Minimum allowed unit voltage = 414V
Maximum allowed voltage = 506V
4. Indoor Motors meet 2010 DOE requirements (Premium Efficient)
5. Refer to High Static Drive Kit Installation Instructions for additional information
6. Refer to H5HK Kit Installation Instructions for additional information
FLA = Full Load Amps
MCA = Minimum Circuit Ampacity
RLA = Rated Load Amps
MOP = Maximum Over-Current Protection
LRA = Locked Rotor Amps
7. Refer to
Table 4, (page 18)
for single circuit MCA/MOP data

Electrical Data

HIGH
COMPRESSORS
STATIC
KIT #
QTY
FACTORY UNIT ELECTRICAL DATA
2 ea.
Factory Std.
2 ea.
2 ea.
Factory Std.
2 ea.
MEDIUM & HIGH STATIC DRIVE ELECTRICAL DATA
2 ea.
921646
2 ea.
2 ea.
921647
2 ea.
2 ea.
921645
2 ea.
ELECTRIC HEAT KIT (FIELD INSTALLED WITH MULTIPLE CIRCUIT KIT # 917468)
ELECTRICAL DATA TABLE - HEATER ONLy
LINE
VOLTAGE
208 / 240
208 / 240
208 / 240
21.63 / 28.80
208 / 240
480
480
480
480
Table 3. H5HK Electrical Data - Multiple Supply Circuits
Table 2
OUTDOOR
MOTORS
(2) EA.
(SEE NOTE 4)
RLA
LRA
FLA
HP
13.1
83.1
2.3
1
6.1
41
1.2
15.6
110
2.3
1.5
7.8
52
1.2
13.1
83.1
2.3
1.5
6.1
41
1.2
13.1
83.1
2.3
2
6.1
41
1.2
15.6
110
2.3
2
7.8
52
1.2
Table 3
ACTUAL
HEATER AMPS
HEATER
(LINE)
KW
6.76 / 9.0
18.76 / 21.65
13.07 / 17.4
36.28 / 41.86
60.0 / 69.3
26.1 / 34.8
72.55 / 83.72
9.9
11.91
18
21.65
28.8
34.64
34.8
41.86
INDOOR
TOTAL
UNIT ONLY
MOTOR
UNIT
RLA
FLA
RLA
MCA
3.2 - 3.1
34.1
37 - 37
1.5
16.1
18
4.4 - 4.2
40.3
44 - 44
2.1
20.1
22
4.4 - 4.2
35.3
39 - 38
2.1
16.7
18
6.0 - 5.8
36.9
40 - 40
2.9
17.5
19
6.0 - 5.8
41.9
46 - 46
2.9
20.9
23
HEATER ONLY CIRCUIT
MCA
23.5 / 27.1
45.3 / 52.3
75.1 / 86.6
90.7 / 104.6
100 / 110
14.9
27.1
43.3
52.3
CIRCUIT
MOP
50 - 50
20
50 - 50
25
50 - 50
20
50 - 50
25
60 - 60
30
MOP
25 / 30
50 / 60
80 / 90
15
30
45
60
17