13 LIST OF ALARMS

There are three types of alarm resets:
— Auto: automatic, when the event causing the alarm stops, also the alarm disappears.
— Semi (semi-automatic) = the alarm is automatic, but if it is triggered more than 3 times in an hour then it becomes with manual reset;
— Manual: manual, to restart normal operation manual acknowledgement is necessary.
ATTENTION: keep the
The alarms log cannot be reset and as the memory available is suitable to contain 100 alarms, once the index has reached the value of 99, its increase will start from 00 again
(over-writing the oldest alarm).
Code
Range
AL01
AL02
AL03
AL04
AL05
AL06
AL07
AL08
AL09
AL10
AL11
AL12
AL13
AL14
AL15
Outlet water temp sensor recovery common faulty or not connected
AL16
AL17
NRP
AL17
NXP
Geothermal input's temperature probe is broken or not connected
AL18
NRP
AL18
NXP
Geothermal output's temperature probe is broken or not connected
AL19
AL21
AL22
AL23
AL24
AL25
AL26
AL27
AL28
NRP
AL28
NXP
AL29
AL30
AL31
AL32
AL33
AL34
AL35
AL36
AL37
AL38
AL39
AL40
AL41
AL42
AL43
AL44
AL45
AL46
AL47
AL48
Discharge gas temperature sensor circuit 1 faulty or not connected
AL49
Discharge gas temperature sensor circuit 2 faulty or not connected
AL50
AL51
AL52
AL53
AL54
AL55
AL56
AL57
AL58
AL59
AL60
AL61
button pressed to rearm the alarm manually.
Description
Clock battery faulty or not connected
Expansion memory damaged
ID8 phase monitor
Board re-start from lost power
High pressure sensor circuit 1 faulty or not connected
High pressure sensor circuit 2 faulty or not connected
Low pressure sensor circuit 1 faulty or not connected
Low pressure sensor circuit 2 faulty or not connected
Inlet water temp sensor evap. faulty or not connected
Evap Out. Temp. broken or disconnected
Outlet water temp sensor evap.com. faulty or not connected
Inlet water temp sensor recovery faulty or not connected
Outlet water temp sensor recovery1 faulty or not connected
Outlet water temp sensor recovery2 faulty or not connected
External temperature sensor faulty or not connected
Circuit 1 Liquid temperature probe broken or not connected
Liquid temperature sensor circuit 2 faulty or not connected
Request for maintenance on compressors of circuit 1
Circuit 1 Pump 1 Rec. maintenance
Circuit 1 Pump 1 Rec. maintenance
Circuit breaker compressor 1 circuit 1
ID13 Pump 1 system overload
ID14 Pump 2 system overload
Thermal alarm heat recovery pump 1
Pump 2 rec. overload
ID15 Fan circuit breaker circuit 1
ID15 Thermal geothermal pump
ID16 Fan circuit breaker circuit 2
Low pressure indicated by pressure switch on circuit 1
Low pressure sensor circuit 1
High pressure indicated by pressure switch on circuit 1
High pressure sensor circuit 1
Circuit 1 Low pressure from probe (not delayed)
Circuit 2 Low pressure from probe (not delayed)
Circ 1 prevention by probe
Circ 2 prevention by probe
Loss of evaporator water flow
Loss of heat recovery water flow
Anti-freeze alarm system inlet/outlet temperature
Anti-freeze alarm system common outlet temperature
Anti-freeze alarm heat recovery 1 inlet/outlet temperature
Anti-freeze alarm heat recovery 2 outlet temperature
Output temp com. rec. anti-freeze
Expansion IO (uPC) Off-line
Expansion IO (pCOe) Off-line
Forcing off recovery 1
Board re-start from lost power
Circuit 1 Comp. 2 maintenance
Circuit 1 Comp.3 maintenance
Circuit 2 Comp.1 maintenance
Circuit 2 Comp.2 maintenance
Circuit 2 Comp.3 maintenance
Circuit 2 Fan maintenance
Circuit 1 Pump 2 Rec. maintenance
Circuit 1 Pump 2 syst. maintenance
Circuit breaker compressor 2 circuit 1
Circuit breaker compressor 3 circuit 1
Circuit breaker compressor 1 circuit 2
Note
Delay
B1
30s
B6
30s
B2
30s
B7
30s
B4
30s
B3
30s
B3 uPC
30s
B1 uPC
30s
B2 uPC
30s
B6 uPC
30s
B4 uPC
30s
B9
30s
ID 6
180s + 3s "M48"
3°C "Ma9"
3°C "Ma9"
3°C "Ma12"
3°C "Ma12"
3°C "Ma12"
20 s
20 s
30 s
30 s
It is not an alarm
Display only
"W18"
Display only
W18"
Display only
W18"
Display only
W18"
Display only
W18"
Display only
W18"
Display only
W18"
Display only
W18"
Reset
Manual
Manual
Manual - 30s
Manual - 30s
Manual - 30s
Manual - 30s
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Semi Automatic
Semi Automatic
Manual
Manual
Manual
Manual
---
---
Semi Automatic
Semi Automatic
Manual
Manual
Manual