5.8 INPUTS/OUTPUTS LIST - ΜPC BOARD
 DIGITAL outputs
NO1
NO2
NO3
NO4
NO5
NO6
NO7 (exchange)
NO8
NO9
NO10
NO11
NO12
Digital inputs
ID1
ID2
ID3
ID4
ID5
ID6
ID7
ID8
ID9
ID10
ANALOGUE outputs
Y1 (0-10V)
Y2 (0-10V)
Y3 (0-10V)
Y4 (0-10V)
Analogue inputs
B1 (NTC)
B2 (NTC)
B3 (NTC)
B4 (NTC)
B5 (NTC)
B6 (NTC)
B7 (NTC)
B7 (NTC)
B8 (NTC)
B9 (NTC; NTC HT;)
B10 (NTC)
B10 (NTC)
B11 (0-5V)
B12 (0-5V)
14
Range
NRP
NXP
NRP
NXP
 
Master
Recovery pump 1
Recovery pump 2
CP3 circuit 1 (CC1B)
CP3 circuit 2 (CC2B)
VS-R (recovery solenoid valve) circuit 1
VS-R (recovery solenoid valve) circuit 2
VS-B (battery solenoid valve) circuit 1
VS-B (battery solenoid valve) circuit 2
VS-E (evaporator solenoid valve) circuit 1
VS-E (evaporator solenoid valve) circuit 2
VBY circuit1
VBY circuit2
Recovery flow switch
Thermomagnetic switch on pump 1 - recovery
Thermomagnetic switch on pump 2 - recovery
Circuit 1 circuit breaker CP3 (MT1B)
Circuit 2 circuit breaker CP3 (MT2B)
On/Off remote D.H.W. /Hot water
Qualify according to setpoint D.H.W.
Recovery inlet water temperature
Recovery 1 outlet water temperature
Evaporator common outlet water temperature (Master/Slave)
Recovery common outlet water temperature (Master/Slave)
DHW storage tank temperature (optional)
Recovery 2 outlet water temperature
Liquid temperature (defrost end) Circuit 1
Geothermal's input water temperature (end of defrosting) Circuit 1
Liquid temperature (defrost end) Circuit 2
Geothermal's output water temperature