FOR PLUGGABLE EQUIPMENT, the socket-outlet shall be installed near the equipment
l
and shall be easily accessible.
CAUTION: The unit is heavy. Lifting the unit requires a minimum of two people.
l

7.4 Operation

Do not disconnect the mains cable on the UPS system or the building wiring outlet
l
(shockproof socket outlet) during operations since this would cancel the protective
earthing of the UPS system and of all connected loads.
The UPS system features its own, internal current source (batteries). The UPS output
l
sockets, or output terminals block may be electrically live even if the UPS system is
not connected to the building wiring outlet.
To fully disconnect the UPS system, first press the OFF/Enter button to disconnect the
l
mains.
Prevent fluids and other foreign objects from entering the UPS.
l
The EPO and USB circuits are an IEC 60950-1 safety extra low voltage (SELV) circuit.
l
This circuit must be separated from any hazardous voltage circuits by reinforced
insulation.
7.5 Maintenance, service, and faults
The UPS system operates with hazardous voltages. Repairs may be carried out only
l
by qualified maintenance personnel.
Caution - risk of electric shock. Even after the unit is disconnected from the mains
l
(building wiring outlet), components inside the UPS system are still connected to the
battery and electrically live and dangerous.
Before carrying out any kind of service and/or maintenance, disconnect the batteries
l
and verify that no current is present, and no hazardous voltage exists in the terminals
of high capability capacitor such as BUS-capacitors.
To avoid electrical shock, turn off the unit and unplug it form the AC power source
l
before servicing the battery.
Only persons are adequately familiar with batteries and with the required
l
precautionary measures may replace batteries and supervise operations.
Caution - risk of electric shock. The battery circuit is not isolated from the input
l
voltage. Hazardous voltages may occur between the battery terminals and the
ground. Before touching, verify that no voltage is present!
Caution - Do not dispose of batteries in a fire. The batteries may explode.
l
Caution - Do not open or mutilate batteries. Released electrolyte is harmful to the
l
skin and eyes. It may be toxic.
A battery can may cause a risk of electrical shock and high short-circuit current. The
l
following precautions should be observed when working on batteries:
a) Remove watches, rings, or other metal objects
b) Use tools with insulated handles.
c) Wear rubber gloves and boots.
d) Do not contact batteries with tools or other metal parts.
e) Disconnect charging source prior to connecting or disconnecting battery terminals.
f) Determine if battery is inadvertently grounded. If inadvertently grounded, remove
source from ground. Contact with any part of a grounded battery can result in
electrical shock.