6. Runtime Chart

Model (VPN)
Battery
Load percentage
100.00%
90.00%
80.00%
70.00%
60.00%
50.00%
40.00%
30.00%
20.00%
10.00%
7. Instructions & Safety Warnings
7.1 Transportation
Transport the UPS system only in the original package to protect from damage.
l
7.2 Preparation
Condensation may occur if the UPS is moved directly from cold to warm environments.
l
The UPS system must be completely dry before being operated. Allow at least two
hours for the UPS system to acclimate to a new environment.
Do not install the UPS near water or wet, high humidity environments.
l
Do not install the UPS where it will be exposed to direct sunlight or near heat sources.
l
Avoid blocking ventilation holes in the UPS enclosure.
l
7.3 Installation
Do not connect appliances or devices which can overload the UPS system (e.g., laser
l
printers).
Route cables to avoid stepping on or tripping over them.
l
Do not connect domestic appliances (such as hair dryers) to the UPS.
l
Connect the UPS system only to an earth-grounded shockproof outlet which must be
l
easily accessible and near the UPS system.
Use only VDE-tested, or UL-marked mains cables (e.g., the mains cable of your
l
computer) to connect the UPS system to the building wiring outlet (shockproof
outlet).
Use only VDE-tested, UL-marked power cables to connect the loads to the UPS.
l
When installing the equipment, ensure that the sum of the leakage current of the UPS
l
and the connected devices does not exceed 3.5mA.
Temperature Rating - Units are considered acceptable for use in a maximum ambient
l
of 40°C (104°F).
UPS2URM3000DC-NC-1N
Minutes
2.64
3.36
4.34
5.53
7.33
9.79
13.51
19.90
32.61
72.53