5. Specifications
MODEL (VPN)
CAPACITY*
INPUT
Low Line Transfer
Low Line
Voltage
Comeback
Range
High Line Transfer
High Line
Comeback
Frequency Range
Phase
Power Factor
THDI
OUTPUT
Output voltage
AC Voltage Regulation
Frequency Range
(Synchronized Range)
Frequency Range
Current Crest Ratio
Harmonic Distortion
AC Mode to Batt.
Transfer
Mode
Time
Inverter to Bypass
Waveform (Batt. Mode)
EFFICIENCY
AC Mode
ECO Mode
Battery Mode
BATTERY
Battery Type
Number
Recharge Time
Charging Current
Charging Voltage
PHYSICAL
Dimension, D X W X H (mm)
Net Weight
With battery
(kgs)
Without battery
ENVIRONMENT
Operation Humidity
Noise Level
MANAGEMENT
Smart RS-232 or USB
SNMP Network
* Derate capacity to 90% of capacity when the output voltage is adjusted to 100VAC.
**For 120VAC system, the output power ratings are different based on different input voltage. (127 is not applicable to USA region)
*** Product specifications are subject to change without further notice.
80VAC/70VAC/60VAC/55VAC ± 5 %
(based on load percentage 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0)
87VAC/77VAC/67VAC/62VAC ± 5 %
THDU < 1.6% @ input and full linear load condition
100/110/115/120/125/127 VAC
50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz (Batt. Mode)
≦ 2 % THD (Linear Load); 4 % THD (Non-linear Load)
3 hours recover to 95% capacity for internal battery@ 2A charging current
Default: 2A, Max: 8A adjustable
20-95 % RH @ 0- 40°C (non-condensing)
Less than 50dBA @ 1 Meter (With fan speed control)
Supports Windows® 2000/2003/XP/Vista/2008/7/8/10, Linux, Unix, and MAC
Power management from SNMP manager and web browser
18
UPS2URM3000DC-NC-1N
3000VA / 2740W
150 VAC ± 5 %
145 VAC ± 5 %
40Hz ~ 70 Hz
Single phase with ground
≧ 0.99 @ full load
≦ 5% @ 80~140VAC
± 1% (Batt. Mode)
47 ~ 53 Hz or 57 ~ 63 Hz
3:1
Zero
< 4 ms
Pure Sinewave
≧91% @ full charged battery
≧96% @ full charged battery
≧90%
12V/9AH
6
82.1 VDC ± 1%
630 x 438 x 88
27.5
12.4
**
Need help?