09: Programmable outlets enable/disable
l
Interface
10: Programmable outlets setting
l
Interface
11: Autonomy limitation setting
l
Interface
12: Battery total AH setting
l
Interface
49Hz. (Default: 47Hz)
For 60Hz output frequency models:
55-59Hz: Set the frequency low loss point from 55Hz to
59Hz. (Default: 57Hz)
Setting
Parameter 2: Enable or disable programmable outlets.
ENA: Programmable outlets enable
DIS: Programmable outlets disable (Default)
Setting
Parameter 2: Set the backup time limits for programmable
outlets.
0-999: Set the backup time limits in minutes from 0-999 for
programmable outlets which connect to non-critical devices
on battery mode. (Default: 999)
Setting
Parameter 2: Set the backup time on battery mode for
general outlets.
0-999: Set the backup time in minutes from 0-999 for
general outlets on battery mode.
DIS: Disable the autonomy limitation and the backup time
will depend on battery capacity. (Default)
Note: Setting to "0", sets backup time to just 10 seconds.
Setting
Parameter 2: Set the battery total AH of the UPS.
7-999: Setting the battery total capacity from 7-999 in AH.
Please set the correct battery total capacity if external
battery bank is connected.