BAC Vertex VRC A-1012N Series Operation & Maintenance Manual page 23

Evaporative condenser
Table of Contents

Advertisement

Belt tension adjustment (if required):
Using a wrench or impact gun, turn the motor base adjusting screw (Figure 7) clockwise to tension the belt or
o
counterclockwise to relieve belt tension. During adjustment of the belt tension, rotate the drives several times by
hand to evenly distribute the tension throughout the belt.
Motor Adjusting Screw
Drive alignment check and adjustment:
Place a straight edge across the driver and the driven sheaves as shown in Figure 8.
o
The straight edge should contact all four points as shown in Figure 8 indicating that the drives are properly
o
aligned.
There should be no more than 1/16" deviation from the four points of contact.
o
In case of realignment, loosen the driver sheave, and align it with the driven sheave. Allow 1/4" for draw-up as
o
the bushing screws are retightened.
Vertex™ Evaporative Condenser Operation & Maintenance Manual – Component Maintenance Procedures
Figure 7. Motor Adjusting Screw
Figure 8. Drive Alignment
Page | 23

Advertisement

Table of Contents
loading

Table of Contents