Start-Up Procedure; Considerations For Initial Start-Up; General; Cleaning - BAC Vertex VRC A-1012N Series Operation & Maintenance Manual

Evaporative condenser
Table of Contents

Advertisement

Start-Up Procedure

Considerations for Initial Start-Up

For units with independent fan control [standard on units with the BALTIDRIVE
For units with VFDs, see Page 54.
For units with vibration cutout switches, see Page 42.

General

If the unit is mounted on vibration isolators or isolation rails (by others), refer to the vibration isolation manufacturer's
guidelines before loading/unloading weight from the unit.
Verify fans and the pump motor are disconnected, locked out, and tagged out.
The unit must be level in both the length and width directions for proper operation.

Cleaning

Drain the basin with the strainer in place.
Remove all dirt and debris from the fan guard(s) and combined inlet shields.
Inspect and clean all spray nozzles.
Clean all the mechanical components, such as the fan and motor.
Remove accumulated dirt and debris from the water guards.
Flush the basin to remove any accumulated dirt and debris.
Remove, clean, and replace the basin strainer.

Inspection

Conduct external inspection of the equipment. Check for leaks, corrosion, and any structural damage.
Conduct internal inspection of the equipment. Check for anything unusual such as structural or mechanical component
damage.
Inspect piping and connections.
Thoroughly inspect the fans for any mechanical or physical damage.
At seasonal start-up or after prolonged shutdown, check the motor insulation with an insulation tester prior to the motor
start-up.
Check and adjust the belt tension. Units equipped with the EC Fan System use direct drive motors and do not require belt
tension.
Vertex™ Evaporative Condenser Operation & Maintenance Manual – Unit Operation and Storage
Power Train], see Page 53.
®
Page | 12

Advertisement

Table of Contents
loading

Table of Contents