3.2

Requirements for installation site

▶ Observe minimum clearances ( Chapter 2.4 on page 50).
▶ Observe minimum room area.
Device type
Installation height
CL5000iU 4CC 35 E
CL5000iU 4CC 53 E
CL5000iU 4C 70 E
CL5000iL 4C 88 E
CL5000iL 4C 105 E
CL5000iL 4C 125 E
CL5000iL 4C 140 E
CL5000iL 4C 160 E
Table 6 Minimum room area
Notices regarding the indoor unit
▶ Do not install the indoor unit in a room in which open ignition sources
(for example: open flames, an operating wall mounted gas boiler or
an operating electric heating system) are in operation.
▶ The installation location must not be higher than 2000 m above sea
level.
▶ Keep the air inlet and air outlet clear of any obstacles to allow the air
to circulate freely. Otherwise poor performance and higher noise
levels may occur.
▶ Keep TV, radio and and similar appliances at least 1 m away from the
unit and the remote control.
▶ Do not install the indoor unit in rooms with a high humidity
(e.g. bathrooms or utility rooms).
▶ Indoor units with a cooling capacity of 2.0 to 5.3 kW are designed for
a single room.
▶ The ceiling construction and suspension system (on site) must be
able to support the weight of the appliance.
Notices regarding the outdoor unit
▶ The outdoor unit must not be exposed to machine oil vapour, hot
spring vapour, sulphur gas, etc.
▶ Do not install the outdoor unit directly next to water or where it is
exposed to sea air.
▶ The outdoor unit must always be kept free of snow.
▶ There must be no disruption caused by extract air or operating noise.
▶ Air should be able to circulate freely around the outdoor unit, but the
appliance must not be exposed to strong wind.
▶ Condensate that forms during operation must be able to drain off
easily. Lay a drain hose if required. In cold regions, installation of the
drain pipe is not advisable as freezing could result.
▶ Place the outdoor unit on a stable base.
3.3

Unit installation

NOTICE
Incorrect assembly can cause material damage.
If the appliance is mounted incorrectly, it may drop off the ceiling
▶ Only mount the appliance on a solid flat ceiling. The ceiling must be
able to carry the weight of the appliance.
▶ Only use screws and wall plugs that are suitable for the ceiling type
and appliance weight.
Climate 5000 L • Climate 5000i U/L – 6721841492 (2022/03)
Minimum room area
2
[m]
[m
]
≥ 2.2
≥ 4
≥ 2.2
≥ 4
≥ 2.2
≥ 6
≥ 2.2
≥ 7
≥ 2.2
≥ 10
≥ 2.2
≥ 12
≥ 2.2
≥ 2.2
3.3.1

Installing the indoor unit in the ceiling

We recommend preparing the pipes before hanging the indoor unit so
that only the pipes need to be connected.
▶ Open the box at the top and lift the indoor unit out and up.
▶ Determine the installation location, taking the minimum clearances
and orientation of the pipes into consideration:  Figs. 4 to 6.
Make sure that the appliance fits between the structural ceiling and
suspended ceiling.
▶ The fascia must be flush with the suspended ceiling.
▶ Define and mark the position of the suspension bolts on the ceiling.
DANGER
Risk of injury!
The ceiling attachment must be suitable for carrying the weight of the
indoor unit. We recommend using threaded rods in order to be able to
adjust the height precisely. Suitable nuts and washers are included in the
scope of delivery of the indoor unit.
DANGER
Risk of injury!
At least two persons are required to hang the appliance and fasten it
securely.
▶ Do not install the appliance on your own.
▶ Hang the appliance on the suspension bolts with the washers and
nuts included in the scope of delivery.
▶ Position the indoor unit at the correct height and align horizontally by
turning the nuts on the threaded rods.
NOTICE
If the appliance is not level condensate may leak out.
▶ Use a spirit level to align the appliance horizontally.
▶ Secure the appliance at the correct installation position with lock
nuts.
▶ Establish pipe connections as described in chapter 3.5.1.
3.3.2

Assembly of cover CL5000iU 4CC ...

▶ Remove the air inlet grille from the cover ( Fig. 20).
▶ Attach cover to the indoor unit with screws provided, paying
attention to orientation ( Fig. 21). The display [2] must be located
opposite the "shorter" side of the L-shaped electronics [1].
▶ The cover must rest evenly and tightly against the indoor unit.
Only reinstall the air inlet grille when establishing the electrical
connection.
Installation
51