Connecting the refrigerant pipe
AA
Refrigerant piping system
Refrigerant piping system table
Max. allowable length
Allowable height length
Temper grade and minimum thickness of the refrigerant pipe
Outer diameter [mm]
ø6.35
ø9.52
ø12.70
ø15.88
ø15.88
ø19.05
ø22.23
CAUTION
• M ake sure to use C1220T-1/2H (Semi-hard) pipe for more than Ø19.05mm. In case of using
C1220T-O (Soft) pipe for Ø19.05mm, pipe may be broken, which can result in an injury.
The appearance of the unit may be different
from the diagram depending on the model.
20 English
Actual pipe length
Actual pipe length
Minimum thickness [mm]
0.7
0.7
0.8
1.0
0.8
0.9
0.9
Make at least one round:
It will reduce noise and vibration
L1
L0
Pipe length or height
AC052NX∗SEC
AC071NX∗SEC
L0 + H + L1
30 m or less
H
15 m or less
CAUTION
• After connecting pipes with knock-out
treatment, plug the space.
• Following the pipe connection, make sure
to proceed precisely to prevent interference
with the internal parts.
H
AC090NX∗SEC
AC100NX∗SGC
AC120NX∗SGC
AC140NX∗SGC
AC160NXMSGC
50 m or less
30 m or less
Temper grade
C1220T-O
C1220T-1/2H
OR