Summary of Contents for Samsung ACN016NDEHA

  • Page 2: Table Of Contents

    Contents Preparation for installation ....................................... 3 Deciding on where to install the indoor unit ................................4 Indoor unit installation ........................................7 Purging the unit ............................................. 8 Connecting the refrigerant pipe ....................................8 Cutting/Flaring the pipes ........................................9 Performing leak test & insulation ....................................10 Drainpipe and drain hose installation ..................................
  • Page 3: Preparation For Installation

    Our units should be installed in compliance with the spaces shown in the installation manual, to ensure accessibility from both Power supply line, fuse or circuit breaker with current local safety standards. to ensure the operation of any other domestic appliance connected to the same electric lines. included in the manual.
  • Page 4: Deciding On Where To Install The Indoor Unit

    Preparation for installation Accessories The following accessories are supplied with the indoor unit. Pattern sheet Thermal insulation Thermal insulation Thermal insulation Flexible hose clamp sponge B sponge C Flexible hose user manual Installation manual Deciding on where to install the indoor unit Indoor unit There must be no obstacles near the air inlet and outlet.
  • Page 5 Thickness: more than 10mm Indoor Unit 400x190 400x190 400x190 400x190 550x550 Insulate the discharge and suction part at the same time when you insulate connection duct. either to guarantee correct operation of maintenance or repairing products. The appearance of the unit maybe different from the picture depending on the model. hanger plate on the corner and carry the indoor unit.
  • Page 6 Deciding on where to install the indoor unit Drawing of the indoor unit Unit : mm Sub duct connection 575*250*575 575*250*575 575*250*575 11.0 11.7 12.0 Liquid pipe connection 1/4" 3/8" 1/2" 5/8" Drain Hose connection OD : Ф32 , ID : Ф25...
  • Page 7: Indoor Unit Installation

    Indoor unit installation 1. Determine the position of the pipe and drain hose hole as seen in the picture and drill the hole with an inner diameter of 65mm so that it slants slightly downwards. Since the diagram is made of paper, it may shrink or stretch slightly due to temperature or humidity.
  • Page 8: Purging The Unit

    Purging the unit before connecting the assembly piping. Unscrew the pinch pipe at the end of each refrigerant pipe. Liquid refrigerant port ready to connect the piping. Connecting the refrigerant pipe There are two refrigerant pipes of different diameters : The inside of copper pipe must be clean &...
  • Page 9: Cutting/Flaring The Pipes

    Cutting/Flaring the pipes 1. Make sure that you have the required tools available. (pipe cutter, reamer, flaring tool and pipe holder) 2. If you wish to shorten the pipes, cut it with a pipe cutter, taking care to ensure that the cut edge remains at a 90° angle with the side of the pipe.
  • Page 10: Performing Leak Test & Insulation

    Performing leak test & insulation Leak test To identify potential gas leaks on the indoor unit, inspect the connection area of each refrigerant pipe using a leak detector for R410A. Before recreating the vacuum and recirculating the refrigerant gas, it is advisable to pressurize the whole system with nitrogen (using a cylinder with pressure reducer) at a pressure above 40 bar in order to immediately detect leaks on the refrigerant fittings.
  • Page 11: Drainpipe And Drain Hose Installation

    e.g. The pipe installed at a corridor of a dormitory and studio or near an exit that opens and closes frequently. Drainpipe and drain hose installation 1 Push the supplied drain hose as far as possible over the drain socket. 2 Tighten the metal clamp as shown in the picture.
  • Page 12: Installing Dpm

    Drainpipe and drain hose installation Concentrated drain pipe Testing the drainage You should test the drainage after completing the installation. check part Prepare a little water about 2.0 liters. 1 Turn the cover drain pump, then pull it out. Hose 2 Pour water into the indoor unit as shown in figure.
  • Page 13: Connecting The Connection Cord

    Connecting the connection cord If using a multi system, refer to the manual supplied with the outdoor unit. the electric connections. The indoor unit is powered by the outdoor unit by means of a H07 RN-F connection cable (or a more power model), with insulation in synthetic rubber and jacket in polychloroprene(neoprene), in accordance with the requirements of standard EN 60335-2-40.
  • Page 14: Setting An Indoor Unit Address And Installation Option

    Setting an indoor unit address and installation option ▶ Set the indoor unit address and installation option with remote controller option. ▶ Please use the proper wireless remocon which can set 24 digit option code. Following is the instructions of setting option ▶...
  • Page 15 Option setting Status ∨ ∧ will be selected in rotation. … 2. Setting Cool mode ∨ ∧ will be selected in rotation. … 4. Setting Dry mode ∨ ∧ will be selected in rotation. … ∨ ∧ will be selected in rotation. …...
  • Page 16 Setting an indoor unit address and installation option Option setting Status 12. Setting Cool mode Press Mode button to be change to Cool mode in the OFF status. ∨ ∧ will be selected in rotation. … 14. Setting Dry mode Press Mode button to be change to Dry mode in the OFF status.
  • Page 17 Setting an indoor unit address (MAIN/RMC) 1. Check whether power is supplied or not. - When the indoor unit is not plugged in, there should be additional power supply in the indoor unit. 2. The panel(display ) should be connected to an indoor unit to receive option. 3.
  • Page 18 Setting an indoor unit address and installation option Setting an indoor unit installation option (suitable for the condition of each installation location) 1. Check whether power is supplied or not. - When the indoor unit is not plugged in, there should be additional power supply in the indoor unit. 2.
  • Page 19 Option Heating setting Motion detect a remote controller compensation sensor Indication Details Indication Details Indication Details Indication Details 0 or 1 Indoor 1 0.No Use (Factory Setting) 1.Standard Mode/Auto Indoor 2 Disuse Set OFF30 Min. Indoor 3 2.Standard Mode/Auto Set OFF60 Min. 3.Standard Mode/Auto 2˚C Set OFF 120 Min.
  • Page 20 Setting an indoor unit address and installation option Changing a particular option You can change each digit of set option. Option The option mode The unit digit of you want to change change will change Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details Indication Option Unit digit...
  • Page 21: Troubleshooting

    Troubleshooting Operation Defrost Timer Filter Remarks Power reset indoor and outdoor unit Detection of the float switch Motion detect sensor error Mixed operation error Flickering X Off...
  • Page 22 "EEE Yönetmeliğine Uygundur" "This EEE is compliant with RoHS"...
  • Page 23: Air Conditioner

    Cassette Type Series NDEHA NDEHA Air Conditioner installation manual This manual is made with 100% recycled paper. imagine the possibilities Thank you for purchasing this Samsung product. To receive more complete service, please register your product at www.samsung.com/register DB98-34365A-2...