Step 5 Connecting the refrigerant pipe

Maximum allowable pipe length [ft(m)]
Model Name
2Ton
AC024BXUPCH
3Ton (single fan)
AC036BXUDCH
3Ton (dual fan)
AC036BXUPCH
4Ton
AC048BXUPCH
5Ton
AC060BXUPCH
outdoor
Recommended liquid and gas pipe diameters [inch(mm)]
Model Name
2Ton
AC024BXUPCH
3Ton (single fan)
AC036BXUDCH
3Ton (dual fan)
AC036BXUPCH
4Ton
AC048BXUPCH
5Ton
AC060BXUPCH
Reuse existing refrigerant lines
To retrofit the outdoor unit by using the existing piping, be sure to:
• Confirm that the existing pipe diameter, length, and height difference between outdoor and indoor unit meet the
requirements list above.
• Confirm that the maximum pressure for the indoor unit is equal or higher than the maximum pressure for the
outdoor unit.
• Confirm that the indoor unit is compatible with R-410A, and utilizes a Thermostatic Expansion Valve (TXV).
If existing indoor unit utilizes an orifice plate, replace the orifice plate with a R-410A TXV.
• Flush the inside of the piping to remove moisture, oil and any other foreign matter.
• Make sure to install a two-way filter dryer on the liquid pipe referring to the figure below.
NOTE
• Make sure to remove the transparent covers at the edge of the pipes before connecting the pipes.
Max pipe length (L1)
98 (30)
164 (50)
164 (50)
164 (50)
98 (30)
indoor
Liquid Pipe Diameter
Two-way filter dryer
(Field supply)
Max pipe height difference between outdoor and indoor unit (h1)
49 (15)
98 (30)
98 (30)
98 (30)
49 (15)
Gas Pipe Diameter
Rated
Min
Max