Step 5 Connecting the refrigerant pipe

Outdoor unit
Main pipe
Items
models
AC052TXADKC
AC071TXADKC
Maximum
AC100TXAD*C
allowable
AC120TXAD*C
length
AC140TXAD*C
AC160TXAD*C
n=1
Outdoor
• Temper grade and minimum thickness of the refrigerant pipe
Outer diameter
Minimum thickness
[mm]
ø 6.35
ø 9.52
ø 12.70
ø 15.88
ø 15.88
ø 19.05
ø 22.23
CAUTION
• Be sure to use C1220T-1/2H (Semi-hard) pipe for more
than Ø19.05 mm. If you use C1220T-O (Soft) pipe for Ø19.05
mm, the pipe may be broken, which can result in an injury.
Make at least one round:
It will reduce noise and vibration
• The appearance of the unit may be different from the
diagram depending on the model.
Max. height difference
between outdoor and
(L1)
indoor units (h1)
30
20
50
30
50
30
75
30
75
30
75
30
indoor
Indoor Unit
L
1
Temper grade
[mm]
0.7
0.7
C1220T-O
0.8
1.0
0.8
C1220T-1/2H OR
0.9
C1220T-H
0.9
Block the
part.
CAUTION
• Cut the pipe outlet to the exact pipe size. In addition,
remove foreign substances and burrs around the outlet.
never tap with a hammer near the pipe outlet.
h
1
Otherwise, it may cause product damage such as
warping of the cabinet.
• After connecting the pipes with pipe outlet, plug the
space around the pipes.
• After connecting the pipes, proceed exactly as directed in
the guide to prevent interference with the internal parts.
• Tighten the nuts to the specified torques. If overtightened,
the nuts could be broken so refrigerant may leak.
• Protect or enclose refrigerant tubing to avoid
mechanical damage.
• After installing pipes, block the unused knock hole
to prevent small animal from entering. However, the
radiant heat hole(A) should be able to intake air.
Step 6 Optional: Cutting and flaring
the pipes
1 Make sure that you have the required tools available.
2 If you wish to shorten the pipes, cut it with a pipe
cutter, taking care to ensure that the cut edge remains
at a 90° angle with the side of the pipe. Refer to the
illustrations below for examples of edges cut correctly
and incorrectly.
Pipe cutter
90°
A
Pipe
Pipe outlet
Oblique
Rough
Burr