13. Troubleshooting Guide

13.1 Refrigeration Cycle System

In order to diagnose malfunctions, make sure that there are no
electrical problems before inspecting the refrigeration cycle.
Such problems include insufficient insulation, problem with the
power source, malfunction of a compressor and a fan.
The normal outlet air temperature and pressure of the refrigeration
cycle depends on various conditions, the standard values for them
are shown in the table on the right.
Difference in the intake
and outlet
air temperatures
Less than 8°C at the cooling mode
Value of electric
current during operation
Lower than specified
Gas side
pressure
More than 8°C
(15 minutes after an
operation is started.)
at cooling mode.
Higher than specified
Cooling Mode
High
Low
Low
Normal Pressure and Outlet Air Temperature (Standard)
Cooling Mode
*Condition: • Indoor fan speed; High
Normal
Dusty condenser
preventing heat radiation
Excessive amount
of refrigerant
Inefficient compressor
Insufficient refrigerant
Clogged strainer or
capillary tube
38
Gas pressure
2
MPa (kg/cm
G)
temperature (°C)
0.9 ~ 1.2 (9 ~ 12)
• Outdoor temperature 35°C at cooling
mode
• Compressor operates at rated frequency
• Measuring the air temperature
difference
• Measuring electric current
during operation
• Measuring gas side pressure
Outlet air
12 ~ 16

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cs-ms12sd3hCs-ms18sd3hCs-ms24sd3h