Panasonic CS-MC95KE Service Manual

Panasonic CS-MC95KE Service Manual

Panasonic multi-split air conditioner
Table of Contents

Advertisement

CONTENTS
Multi-Split Air Conditioner
CS-MC95KE CU-MC145KE
CS-MC95KE CU-MC185KE
CS-MC95KE CU-3MC205KE
CS-MC125KE CU-MC245KE
CS-MC76KE
CS-MC126KE CU-MC196KE
Page
2
3
6
16
20
23
28
33
© 2000 Matsushita Industrial Corp. Sdn. Bhd.
(11969-T) All rights reserved. Unauthorized copying
and distribution is a violation of law.
Order No: MAC0011057C2
Page
41
65
76
83
90
94
96
104

Advertisement

Table of Contents
loading

Summary of Contents for Panasonic CS-MC95KE

  • Page 1: Table Of Contents

    Order No: MAC0011057C2 Multi-Split Air Conditioner CS-MC95KE CU-MC145KE CS-MC95KE CU-MC185KE CS-MC95KE CU-3MC205KE CS-MC125KE CU-MC245KE CS-MC76KE CS-MC126KE CU-MC196KE CONTENTS Page Page 1 Features 9 Operating Instructions 2 Functions 10 Installation Instructions 3 Product Specifications 11 3-way Valve 4 Dimensions 12 2-way, 3-way Valve...
  • Page 2: Features

    CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE 17 Replacement Parts List 25 Replacement Parts List 18 Exploded View 26 Exploded View 19 Replacement Parts List 27 Replacement Parts List 20 Exploded View...
  • Page 3: Functions

    CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE 2 Functions Remote Control Self illuminating button OFF / ON I TEMP. Operation OFF / ON Room Temperature Setting • Temperature Setting (16°C to 30°C) •...
  • Page 4: Indoor Unit

    CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE Indoor Unit AUTO OFF / ON Automatic Operation Button Random Auto Restart Control • Press for < 5s to operate Automatic • Operation is restarted randomly after operation mode.
  • Page 5: Outdoor Unit

    CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE Outdoor Unit CU-MC245KE CU-MC145KE / CU-MC185KE / CU-MC196KE / CU-3MC205KE Compressor Reverse Rotation Protection Control • To protect compressor from reverse rotation when there is a instantaneous power failure.
  • Page 6: Product Specifications

    CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE 3 Product Specifications Unit CS-MC95KE CU-MC145KE Cooling Capacity (1 unit) 2.82 - 2.78 (2 units) 1.81 × 2 - 1.79 × 2 kcal/h 2,430 - 2,390 1,555 ×...
  • Page 7 CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE Heat Exchanger Description Evaporator Condenser Tube material Copper Copper Fin material Aluminium Aluminium Fin Type Slit Fin Louver Fin Row / Stage (Plate fin configuration, forced draft) 2 ×...
  • Page 8 CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE Unit CS-MC95KE CU-MC185KE Cooling Capacity (1 unit) 2.44 - 2.40 (2 units) 2.44 × 2 - 2.40 × 2 kcal/h 2,100 - 2,060 2,100 × 2 - 2,065 × 2 Moisture Removal (1 unit) 1.5...
  • Page 9 CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE Heat Exchanger Description Evaporator Condenser Tube material Copper Copper Fin material Aluminium Aluminium Fin Type Slit Fin Louver Fin Row / Stage (Plate fin configuration, forced draft) 2 ×...
  • Page 10 CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE CS-MC95KE CU-3MC205KE Unit Single Operation Single Operation Double Operation Trible (A, B1, B2) Operation (B1 or B2) (B1 + B2) (A + B1 or B2) (A + B1 + B2) Cooling Capacity Per Unit —...
  • Page 11 CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE Heat Description Evaporator Condenser Exchanger Tube material Copper Copper Fin material Aluminium Aluminium Fin Type Slit Fin Louver Fin Row / Stage (Plate fin configuration, forced draft) 2 ×...
  • Page 12 CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE Unit CS-MC125KE CU-MC245KE Cooling Capacity (1 unit) 3.50 - 3.45 (2 units) 3.50 × 2 - 3.45 × 2 kcal/h 3,010 - 2,970 3,010 × 2 - 2,970 × 2 Moisture Removal (1 unit) 2.1...
  • Page 13 CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE Heat Exchanger Description Evaporator Condenser Tube material Copper Copper Fin material Aluminium Aluminium Fin Type Slit Fin Louver Fin Row / Stage (Plate fin configuration, forced draft) 2 ×...
  • Page 14 CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE Unit CS-MC126KE CS-MC76KE CS-MC196KE Cooling Capacity (A) 3.55 - 3.52 (B) 2.08 - 2.06 (A+B) 5.63 - 5.58 kcal/h (A) 3,050 - 3,030 (B) 1,790 - 1,770...
  • Page 15 CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE Heat Exchanger Description Evaporator Condenser Tube material Copper Copper Fin material Aluminium Aluminium Fin Type Slit Fin Louver Fin Row / Stage (Plate fin configuration, forced draft) (A) 2 ×...
  • Page 16: Dimensions

    CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE 4 Dimensions...
  • Page 17 CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE...
  • Page 18 CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE...
  • Page 19 CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE...
  • Page 20: Refrigeration Cycle Diagram

    CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE 5 Refrigeration Cycle Diagram...
  • Page 21 CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE...
  • Page 22 CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE...
  • Page 23: Block Diagram

    CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE 6 Block Diagram...
  • Page 24 CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE...
  • Page 25 CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE...
  • Page 26 CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE...
  • Page 27 CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE...
  • Page 28: Wiring Diagram

    CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE 7 Wiring Diagram...
  • Page 29 CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE...
  • Page 30 CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE...
  • Page 31 CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE...
  • Page 32 CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE...
  • Page 33: Operation Details

    CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE 8 Operation Details 8.1. Cooling Mode Operation Cooling in operation according to Remote Control setting. Time Delay Safety Control (3 minutes) • When the compressor is stopped by Remote Control, it restarts after 3 minutes when the Remote Control is turned ON.
  • Page 34 CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE Automatic Fan Speed Mode When Automatic Fan Speed is selected at Remote Control during cooling operation. • Fan speed rotates in the range of Hi to Me.
  • Page 35: Soft Dry Mode Operation

    CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE 8.2. Soft Dry Mode Operation • The unit starts cooling operation until the room temperature reaches the setting temperature set on the Remote Control, and then Soft Dry operation will start.
  • Page 36 CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE Soft Dry Operation Time Diagram...
  • Page 37: Air Circulation Mode Operation

    CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE 8.3. Air Circulation Mode Operation • When the temperature near the ceiling reaches the setting temperature, Air Circulation Mode operation commences at low airflow volume. It stops when the temperature drops to 2°C below the setting temperature.
  • Page 38: Powerful Mode Operation

    CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE 8.5. Sleep Mode Auto Operation Cooling or Soft Dry Operation When you press the SLEEP Mode, the following movement will start to avoid overcooling.
  • Page 39: Random Auto Restart Control

    CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE 8.8. Random Auto Restart Control • If there is a power failure, operation will be automatically restarted after 3 to 5 1/2 minutes when the power is resumed.
  • Page 40: Airflow Direction Control

    CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE 8.10. Airflow Direction Control Airflow Direction Auto-Control • When set a Airflow Direction Auto-Control with remote control, the louver swings up and down as shown in the diagram.
  • Page 41: Operating Instructions

    CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE 9 Operating Instructions SAFETY PRECAUTIONS Before operating, please read the following “Safety Precautions” carefully. To prevent personal injury, injury to others and property damage, the following instructions must be followed.
  • Page 42: Operation Precautions

    CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE Operation Precautions Do not insert plug to operate the unit. Warning Do not pull out plug to stop the unit. This sign warns of death or serious injury.
  • Page 43 CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE Switch off the power supply if the unit is Caution not used for a long period. This sign warns of injury. Do not pull the cord to disconnect the plug.
  • Page 44: Name Of Each Part

    CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE NAME OF EACH PART Indoor Unit Air Intake Vent Front Panel Power Supply Cord Panel Opener Signal Receptor Horizontal Airflow Direction Air Outlet Vent...
  • Page 45 CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE Accessories Outdoor Unit CU-MC185KE CU-MC196KE Ground Terminal (Inside Cover) Air Intake Vents (Rear) Piping (Side) Remote Control Drain Hose Connecting cable Air Outlet Vents...
  • Page 46 CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE Remote Control Operation Display Signal Transmitter OFF/ON Button (Self-illuminating Button) Room Temperature Setting Button (Self-illuminating Button) Powerful Mode Operation Button When the remote control cover is opened...
  • Page 47: How To Use The Remote Control

    CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE How to use the remote control Notes • Do not throw or drop • Do not get it wet • Certain type of flourescent lamps may affect signal reception.
  • Page 48: Preparation Before Operation

    CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE PREPARATION BEFORE OPERATION Indoor Unit Warning Ensure the power plug is securely inserted. A loose plug may cause a fire or an electric shock.
  • Page 49: Setting The Clock

    CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE Remote Control Inserting batteries OPEN Slide the cover to open Be sure the directions are correct • Open the remote control cover and confirm the display 12:00 PM is flashing.
  • Page 50: How To Operate

    CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE HOW TO OPERATE Automatic, Cooling, Soft Dry, Fan Press to select the desired operation mode Display When pressed, the display changes in this order.
  • Page 51 CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE Adjusting Airflow Direction And Fan Speed Press to select Fan speed • The display changes in this order Automatic Medium High Selecting Vertical Airflow Direction Press AUTO, •...
  • Page 52: Setting The Timer

    CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE SETTING THE TIMER Ensure that the current time is correct before setting the timer. The timer cannot be set if the time display is flashing.
  • Page 53 CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE Recommended Setting of Timer When you sleep • Set the time at which you will go to sleep with the OFF-TIMER. This prevent wastage of electricity.
  • Page 54: Convenience Operation

    CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE CONVENIENCE OPERATION Sleep Mode This is to obtain a comfortable room temperature while sleeping. To set the sleep mode, press SLEEP. * The sleep indicator on the indoor unit will light up.
  • Page 55 CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE Economy or Powerful Mode Economy and Powerful operation cannot be selected simultaneously. Economy Mode To save electrical power consumption. However, please use this mode when the room have reached your desired temperature.
  • Page 56: Care And Maintenance

    CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE CARE AND MAINTENANCE Cleaning the Indoor Unit and Remote Control • Wipe gently with a soft, dry cloth. • Do not clean with water hotter than 40°C or with polishing fluids.
  • Page 57: Cleaning The Front Panel

    CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE Cleaning the Front Panel (Must be removed before washing) Caution • Do not touch the metal parts in • Do not leave water on the •...
  • Page 58 CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE Replacing the Air Purifying Filters (Once every 3 month) • Do not reuse dirty filters. Consult the nearest authorized dealer. (Air Purifying filter No. CZ-SFD50N) •...
  • Page 59 CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE Pre-season Inspection • Is the discharge air cold? Operation is normal if 15 minutes after the start of operation, the difference between the air intake and outlet vents temperatures is 8°C or above for cooling.
  • Page 60: Troubleshooting

    CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE TROUBLESHOOTING Normal Operation - Is it okay? - This is the answer. - Air conditioner has been restarted, but does not operate for 3 minutes.
  • Page 61: Abnormal Operation

    CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE Abnormal Operation Hmmm! The air conditioner does not operate. Air conditioner operation noise too loud. • Has a circuit breaker been tripped? • Is the installation work slanted? •...
  • Page 62: Helpful Information

    CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE HELPFUL INFORMATION Auto Operation Button Automatic Operation • If the remote control fails to function or misplaced, press Auto Operation button for Automatic operation.
  • Page 63: Energy Saving And Operation Hints

    CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE ENERGY SAVING AND OPERATION HINTS Air Filter and Air Purifying Filter Clean the air filter every 2 weeks and change the Air Purifying Filter every 3 months.
  • Page 64 CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE Warning 1) This appliance must be earthed. 2) If the supply cord is damaged or need to be replaced, it must be replaced by the manufacturer or its service agent or a similarly qualified person in order to avoid a hazard.
  • Page 65: Installation Instructions

    CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE 10 Installation Instructions Required tools for Installation Works 1. Phillips screw driver 5. Spanner 9. Gas leak detector 13. Multimeter 2. Level gauge 6. Pipe cutter 10.
  • Page 66 CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE 1. Grounding is necessary. It may cause electrical shock if grounding is not perfect. 2. Do not install the unit at place where leakage of flammable gas may occur. In case gas leaks and accumulates at surrounding of the unit, it may cause fire.
  • Page 67 CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE Attached accessories Piping size Common Max. Max. Additional Length Elevation Piping Refrigerant Model Gas Liquid Length (g/m) CU-MC145E 3/8” 1/4” CU-MC185KE 3/8” 1/4” CU-3MC205KE 3/8”...
  • Page 68: Select The Best Location

    CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE 10.2. INDOOR UNIT 10.2.1. SELECT THE BEST LOCATION (Refer to “Select the best location” section) 10.2.2. HOW TO FIX INSTALLATION PLATE The mounting wall is strong and solid enough to prevent it from the vibration.
  • Page 69: Indoor Unit Installation

    CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE 10.2.3. TO DRILL A HOLE IN THE WALL AND INSTALL A SLEEVE OF PIPING 1. Insert the piping sleeve to the hole. 2. Fix the bushing to the sleeve.
  • Page 70 CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE (This can be used for left rear piping and left bottom piping also.)
  • Page 71 CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE 10.2.5. CONNECT THE CABLE TO THE HOW TO TAKE OUT FRONT GRILLE INDOOR UNIT Please follow below steps to take out front grille if necessary such as when servicing.
  • Page 72: Install The Outdoor Unit

    CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE 10.3. OUTDOOR UNIT 10.3.1. SELECT THE BEST LOCATION MODEL Piping size (Torque) Liquid (Refer to “Select the best location” CU-MC145KE 3/8” (42 N.m) 1/4” (18 N.m)
  • Page 73: Evacuation Of The Equipment

    CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE CUTTING AND FLARING THE PIPING 1. Please cut using pipe cutter and then remove the burrs. 2. Remove the burrs by using reamer. If burrs is not removed, gas leakage may be caused.
  • Page 74: Pipe Insulation

    CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE 10.3.5. CONNECT THE CABLE TO THE 10.3.6. PIPE INSULATION OUTDOOR UNIT 1. Please carry out insulation at pipe connection portion as mentioned in Indoor/Outdoor Unit Installation Diagram.
  • Page 75 CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE CHECK ITEMS Is there any gas leakage at flare nut connections? Has the heat insulation been carried out at flare nut connection? Is the connecting cable being fixed to terminal board firmly?
  • Page 76: 11 3-Way Valve

    CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE 11 3-way Valve CU-MC145KE / CU-MC185KE / CU-3MC205KE / CU-MC196KE 3-way Valve (Liquid Side) 3-way Valve (Gas Side) Works Shaft Position Service Port Shaft Position...
  • Page 77: Evacuation Of Installation

    CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE 11.1. Evacuation of Installation When installing an air conditioner, be sure to evacuate the air inside the indoor unit and pipes in the following procedure.
  • Page 78: Pumping Down

    CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE 11.2. Pumping down Procedure: 1. Confirm that both the 3-way valves are set to the 6. Operate the air conditioner at the cooling cycle and opened position.
  • Page 79 CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE 11.3. Evacuation of Re-installation WHEN REINSTALLING AN AIR CONDITIONER, BE SURE TO If air remain in the indoor unit and refrigeration pipes, it will...
  • Page 80 CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE 11.4. Balance refrigerant of the 3-way valves (Lack of refrigerant in the refrigeration cycle) Procedure: 1. Confirm that both the 3-way valves are set to the opened position.
  • Page 81 CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE 11.5. Evacuation (No refrigerant in the refrigeration cycle) Procedure: 1. Connect the vacuum pump to the charge set’s centre hose. 2. Turn on the vacuum pump to evacuate the unit.
  • Page 82: Gas Charging

    CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE 11.6. Gas charging (After Evacuation) Procedure: 1. Connect the charge hose to the charging cylinder. 5. Mount the valve stem nuts and the service port caps onto the 3-way valves.
  • Page 83: 12 2-Way, 3-Way Valve

    CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE 12 2-way, 3-way Valve CU-MC245KE 2-way Valve (Liquid Side) 3-way Valve (Gas Side) Works Shaft Position Shaft Position Service Port Shipping Close Closed Closed...
  • Page 84 CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE 12.1. Evacuation of Installation WHEN INSTALLING AN AIR CONDITIONER, BE SURE TO If air remain in the indoor unit and refrigeration pipes, it will...
  • Page 85 CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE 12.2. Pumping down Procedure: 1. Confirm that both the 2-way and 3-way valves are set to 6. Operate the air conditioner at the cooling cycle and the opened position.
  • Page 86 CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE 12.3. Evacuation of Re-installation WHEN REINSTALLING AN AIR CONDITIONER, BE SURE TO If air remain in the indoor unit and refrigeration pipes, it will...
  • Page 87 CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE 12.4. Balance refrigerant of the 2-way, 3-way valves (Lack of refrigerant in the refrigeration cycle) Procedure: 1. Confirm that both the 2-way and 3-way valves are set to the open position.
  • Page 88 CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE 12.5. Evacuation (No refrigerant in the refrigeration cycle) Procedure: 1. Connect the vacuum pump to the charge set’s centre hose. 2. Evacuation for approximately one hour.
  • Page 89 CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE 12.6. Gas charging (After Evacuation) Procedure: 1. Connect the charge hose to the charging cylinder. • Connect the charge hose which you disconnected from This is different from previous procedures.
  • Page 90: Servicing Information

    CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE 13 Servicing Information • Inspection points for the Indoor Electronic Controller 1. The Electronic Controller, a signal Receiver and an Indicator () can be seen by the below steps: −...
  • Page 91 CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE 2. Remove the Fan Motor by:- − Release the Fan motor leadwire by pressing the hook at the center of the connector. ( − Then remove the particular piece that holding the fan motor by pressing the tab.
  • Page 92 CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE • Cross Flow Fan Removal Procedure. 1. Remove the control board and the fan motor by referring to the “Indoor Fan Motor Removal Procedure”.
  • Page 93 CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE • Remote Control Reset When the batteries are inserted for the first time, or the batteries are replaced, all the indications will blink and the remote control might not work.
  • Page 94: Troubleshooting Guide

    CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE 14 Troubleshooting Guide 14.1. Refrigeration cycle system In order to diagnose malfunctions, make sure that there are no electrical problems before inspecting the refrigeration cycle.
  • Page 95: Diagnosis Methods Of A Malfunction Of A Compressor

    CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE 14.1.1. Relationship between the condition of the air conditioner and pressure and electric current Cooling Mode Condition of the air conditoner Low Pressure High Pressure...
  • Page 96: Technical Data

    CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE 15 Technical Data 230V Outdoor Temp. (°C) Indoor wet bulb temp. 17.0°C 2.80 2.12 1.05 2.61 2.03 1.13 2.43 1.95 1.21 2.21 1.86 1.31 19.0°C...
  • Page 97 CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE 220V Outdoor Temp. (°C) Indoor wet bulb temp. 17.0°C 3.55 2.69 1.06 3.32 2.58 1.14 3.09 2.48 1.22 2.81 2.36 1.32 19.0°C 3.58 1.16 19.5°C...
  • Page 98 CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE 230V Outdoor Temp. (°C) Indoor wet bulb temp. 17.0°C 2.80 2.12 1.03 2.61 2.03 1.10 2.43 1.95 1.18 2.21 1.86 1.27 19.0°C 2.82 1.12 19.5°C...
  • Page 99 CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE 230V Outdoor Temp. (°C) Indoor wet bulb temp. 17.0°C 5.95 4.51 1.70 5.56 4.33 1.83 5.17 4.16 1.96 4.70 3.95 2.11 19.0°C 6.00 1.86 19.5°C...
  • Page 100 CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE 230V Outdoor Temp. (°C) Indoor wet bulb temp. 17.0°C 3.52 2.67 1.15 3.29 2.56 1.23 3.06 2.46 1.32 2.78 2.34 1.42 19.0°C 3.55 1.25 19.5°C...
  • Page 101 CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE...
  • Page 102 CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE...
  • Page 103 CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE...
  • Page 104: Exploded View

    CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE 16 Exploded View Note: The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
  • Page 105: Replacement Parts List

    CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE 17 Replacement Parts List <Model: CS-MC76KE / CS-MC95KE> DESCRIPTION & NAME Q’TY CS-MC76KE CS-MC95KE REMARKS ← CHASSY COMPLETE CWD50C338 ← PARTICULAR PIECE CWD931019 FAN MOTOR...
  • Page 106: Exploded View

    CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE 18 Exploded View Note: The above exploded view is for the purpose of parts disassembly and replacement.
  • Page 107: Replacement Parts List

    CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE The non-numbered parts are not kept as standard service parts. 19 Replacement Parts List <Model: CS-MC125KE / CS-MC126KE> DESCRIPTION & NAME Q’TY CS-MC125KE CS-MC126KE REMARKS ←...
  • Page 108: Exploded View

    CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE 20 Exploded View Note: The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
  • Page 109: Replacement Parts List

    CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE 21 Replacement Parts List <Model: CU-MC145KE> DESCRIPTION & NAME Q’TY CU-MC145KE REMARKS BASE ASS’Y CWD50K573A SOUND PROOF COVER CWH15066 FAN MOTOR BRACKET CWD54168 CONDENSER...
  • Page 110: Exploded View

    CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE 22 Exploded View Note: The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
  • Page 111: Replacement Parts List

    CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE 23 Replacement Parts List <Model: CU-MC185KE> DESCRIPTION & NAME Q’TY CU-MC185KE REMARKS BASE ASS’Y CWD50K663A AIR GUIDER FOR P.F. CWD31094A SOUND PROOF COVER CWH15071...
  • Page 112: Exploded View

    CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE 24 Exploded View Note: The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
  • Page 113: Replacement Parts List

    CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE 25 Replacement Parts List <Model: CU-3MC205KE> DESCRIPTION & NAME Q’TY CU-3MC205KE REMARKS BASE FAN ASS’Y CWD50K663A COMPRESSOR 2PS193D2AA01 AIR GUIDER CWD31094A SOUND PROOF COVER...
  • Page 114: Exploded View

    CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE 26 Exploded View Note: The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
  • Page 115: Replacement Parts List

    CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE 27 Replacement Parts List <Model: CU-MC245KE> DESCRIPTION & NAME Q’TY CU-MC245KE REMARKS CHASSY ASS’Y (UPPER) CWD50K625A FAN MOTOR BRACKET CWD54171 SCREW - FAN MOTOR BRACKET...
  • Page 116: Exploded View

    CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE 28 Exploded View Note: The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
  • Page 117: Replacement Parts List

    CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE 29 Replacement Parts List <Model: CU-MC196KE> DESCRIPTION & NAME Q’TY CU-MC196KE REMARKS BASE ASS’Y CWD50K662A COMPRESSOR A 2KS224D5CA02 MOUNT RUBBER CWH50055 CWH4582065 SOUND PROOF MATERIAL...
  • Page 118: Electronic Parts List

    CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE 30 Electronic Parts List <Electronic Controller Part No.: CWA742323> SYMBOL DESCRIPTION & NAME PART NO. SOUND GENERATOR A48040 D1, D4 DIODE A541SR154-4 DIODE A54CS1VB20E...
  • Page 119: Electronic Circuit Diagram

    CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE 31 Electronic Circuit Diagram • CS-MC95KE / CU-MC145KE • CS-MC95KE / CU-MC185KE • CS-MC95KE / CU-3MC205KE • CS-MC125KE / CU-MC245KE • CS-MC76KE • CS-MC126KE / CU-MC196KE...
  • Page 120 CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE SCHEMATIC DIAGRAM 2/3 RY-PWR DRIVE RY-PWR 2SD148-4X 4.7k 2.2k ERA15-01 6.2k 4.7k A55DC143XKTX RELAY DRIVE A55DC143XKTX RELAY DRIVE A52D0001G502 S1VD20 – A52BR9020F 5.1k RELAY DRIVE RELAY DRIVE 0.1µ...
  • Page 121 CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE SCHEMATIC DIAGRAM 3/3 AC 220-230V 50/60Hz 102 C THERMAL FUSE CN-FUSE2 CN-FUSE1 (WHT) RY-PWR OVER LOAD PROTECTOR FUSE RY-M RY-H RY-SHI SSR1 ZNR2 YELLOW...
  • Page 122 CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE...
  • Page 123 CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE How to use electronic circuit diagram TIMER TABLE Test Mode Name Time (When test point Remarks Short-circuited) Sleep Mode Waiting 1 hr. 6 sec.
  • Page 124 CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE 31.1. REMOTE CONTROL...
  • Page 125: Print Pattern Indoor Unit Printed Circuit Board

    CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE 31.2. PRINT PATTERN INDOOR UNIT PRINTED CIRCUIT BOARD TOP VIEW...
  • Page 126 CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE 31.3. PRINT PATTERN INDOOR UNIT PRINTED CIRCUIT BOARD BOTTOM VIEW...
  • Page 127 CS-MC95KE CU-MC145KE / CS-MC95KE CU-MC185KE / CS-MC95KE CU-3MC205KE / CS-MC125KE CU-MC245KE / CS-MC76KE / CS-MC126KE CU-MC196KE [MACC] Printed in Malaysia...

Table of Contents