SAVE THESE INSTRUCTIONS
This manual contains instructions and warnings that should be followed during the installation, operation and storage of this product. Failure to heed these warnings may affect your warranty.
Please recycle Tripp Lite Products. The batteries used in Tripp Lite products are sealed Lead-Acid batteries. These batteries are highly recyclable. Please refer to your local codes for disposal requirements.
You can call Tripp Lite for recycling info at 1.773.869.1234.
You can go to the Tripp Lite Website for up-to-date information on recycling the batteries or any Tripp Lite product. Please follow this link: http://www.tripplite.com/support/recycling-program/
STEP 1: To install the UPS in a 4-post rack, attach the included mounting hardware to the UPS as shown in diagram A. To mount the UPS in a 2-post rack, attach the included hardware to the UPS as shown in diagram B. Then, using an assistant if necessary, lift the UPS and attach it to a standard rack or rack enclosure with usersupplied hardware.
If the UPS is placed flat on a surface, do NOT stack any other object directly on top of the unit.
The UPS will stand in a tower position without the aid of the included hardware. However, for added stability Tripp Lite recommends that the included hardware be attached as shown in diagram C. The UPS and included hardware are designed for common rack and rack enclosure types and may not be appropriate for all applications.
STEP 2: Plug the UPS into a properly grounded outlet.
After plugging the UPS into a wall outlet, push the button for two seconds to turn the UPS on (see Basic Operation section).
The UPS will not turn on automatically in the presence of live utility power.
Note: UPS system will function properly upon initial startup; however, maximum runtime for the unit's battery will only be accessible after it has been charged for 24 hours.
STEP 3: Plug your equipment into the UPS.
* Your UPS is designed to support electronic equipment only. You will overload the UPS if the total VA ratings for all the equipment you connect to the outlets exceeds the UPS's Output Capacity. To find your equipment's VA ratings, look on their nameplates. If the equipment is listed in amps, multiply the number of amps by 120 to determine VA. (Example: 1 amp × 120 = 120 VA).If you are unsure if you have overloaded the outlets, run a self-test (see Self-Test description in Basic Operation section).
STEP 4: Optional Installation.
All models include USB and RS-232 communication ports as well as Tel/DSL/network surge protection jacks. These connections are optional; the UPS will work properly without these connections. See the connector's description in the Basic Operation section for connection instructions.
If the LINE POWER icon does not illuminate when the UPS is turned ON, try the following:
The LCD indicates a variety of UPS operational conditions. All descriptions apply when the UPS is plugged into an AC outlet and turned on. The LCD can be rotated for easy viewing, regardless of whether the UPS is in a horizontal or vertical ("tower") position. To rotate the display, insert a small tool in the slots on the sides of the display to pop it out of the UPS housing; rotate the display, and snap it back into the UPS housing.
Tap the button to advance from one display to the next. Use the button to toggle settings for Power Sensitivity Control, External Battery Setting Control, Scroll Control, Alarm, LCD Brightness and Self-test functions. The last option displayed before navigating away from this menu option will be the selected setting. When the preferred setting has been selected, continue by pressing the button. If the screen is idle for 20 seconds, the LCD will return to the home screen, retaining the last selected settings.
Use the button to advance through power conditions.
* Load Wattage is displayed in watts up to "999", and then will be displayed in Kilowatts.
Tap the button repeatedly to advance to the LCD screen featuring the icon. Press the button to select ON or OFF alarm mode settings. The last option displayed before navigating away from this menu option will be the selected setting.
Tap the button repeatedly to advance to the LCD Brightness screen marked "LCD". Press the button to select Medium Backlight (default), High Backlight or Dim Backlight. The last option displayed before navigating away from this menu option will be the selected setting.
Note: After 2 minutes of inactivity, the backlight will revert to the Dim setting until a button is pressed.
Tap the button repeatedly to advance to the TEST BATT screen. Press the button to initiate the test. The test will last approximately 10 seconds as the UPS switches to battery to test the capacity with a load. Upon completion of the test, the screen will indicate PAS or BAD (pass or bad) for 20 seconds, then return to the home screen. Connected equipment can remain on during the test. Do not unplug your UPS, this will remove safe electrical grounding.
Tap the button repeatedly to advance to Sensitivity screen, as shown here:
Press the button to advance through the options. The last option displayed, before navigating away from this menu option, will be the selected setting.
This setting is normally set to 100%, which enables the UPS to protect against waveform distortions in its AC input. When such distortion occurs, the UPS will normally switch to providing PWM sine wave power from its battery reserves for as long as the distortion is present. In some areas with poor utility power or where the UPS's input power comes from a backup generator, frequent brownouts and/or chronic waveform distortion could cause the UPS to switch to battery too often, draining its battery reserves. You may be able to reduce how often your UPS switches to battery due to waveform distortion or brownouts by experimenting with different settings. As the setting is reduced, the UPS becomes more tolerant of variations in its input power's AC waveform.
Note: When experimenting with different settings, operate connected equipment in a safe test mode so that the effect on the equipment of any waveform distortions in the UPS's output can be evaluated without disrupting critical operations. The experiment should last long enough to assure that all expected line conditions are encountered.
Tap the button repeatedly to advance to the Scroll screen as shown here:
Press the button to advance to the next available option. The last option displayed, before navigating away from this menu option, will be the selected setting.
This display option allows the user to select the option to automatically scroll each operating condition of the UPS (such as Input Voltage, Output Voltage and Runtime) automatically.
Notes:
Tap the button repeatedly to advance to the External Battery screen, as shown here:
Press the button to advance to the next available option. The last option displayed, before navigating away from this menu option, will be the selected setting.
Note: The Battery Runtime calculation is based on this setting.
This feature setting allows the user to configure the UPS for use with an External Battery Pack or without an External Battery Pack. The Runtime will be automatically reconfigured.
Note: Battery Packs cannot be daisychained. Only one Battery Pack can be attached to the UPS.
In the event the UPS battery requires replacement, the icon will flash, as well as the icon. If there is an overload, the , and icons will flash simultaneously along with a numeric read out of the load percentage.
ON/OFF/MODE Button: Press and hold for 2 seconds to turn on the UPS and 2.5 seconds to turn the UPS off. When the UPS is on, tap this button repeatedly to advance through LCD screens. If utility power is absent, pressing and holding this button for 2.5 seconds will "cold-start" the UPS; i.e. turn it on and supply power to the outlets from its batteries.
MUTE/ENTER Button: Use this button to toggle selection options for: self-test, enable/disable alarm, LCD brightness, Sensitivity Control, Scroll Control and the External Battery Setting Control. This button can also be used to temporarily mute an active alarm by briefly pressing it.
Tel/DSL Line Protection Jacks: These jacks protect equipment against surges over a single phone line. Connecting your equipment to these jacks is optional. Your UPS will work properly without this connection. An RJ-11 cable is included with your UPS.
USB and RS-232 Communication Ports: These ports can connect your UPS to any computer for automatic file saves and unattended shutdown in the event of a power failure. Use with Tripp Lite's PowerAlert Software (available as a FREE download at www.tripplite.com) and appropriate USB or DB9 cable. Both a USB and a DB9 cable are included with your UPS.
Notes:
Battery Backup Protected/Surge Protected Outlets: Provide both battery backup and surge protection. Plug your computer, monitor and other critical equipment into these outlets.
Note: Do not plug laser printers into the UPS.
Removable Mounting Hardware: Adapts the UPS to either tower or rack-mount (2U) applications.
External Battery Connector (XL model only): Use to connect a Tripp Lite external battery pack for additional runtime. Only use the Tripp Lite BP24V15RT2U external battery pack (rated 24Vdc, 14Ahr with overcurrent protection). Refer to instructions available with the battery pack for complete connection information and safety warnings.
Note: Visit Tripp Lite on the Web at www.tripplite.com/support to locate the specific battery for your UPS.
Resettable Input Circuit Breaker: Protects your electrical circuit from overcurrent draw from the UPS load. If this breaker trips, remove some of the load, then reset it by pressing it in.
Under normal conditions, the original battery in your UPS will last several years. Battery replacement should only be performed by qualified personnel. Refer to "Battery Warnings" in the Important Safety Warnings section for complete battery safety information.
The SMART1200LCD UPS system requires a Tripp Lite RBC1200 replacement battery cartridge. The SMART1500LCD UPS system requires a Tripp Lite RBC1500 replacement battery cartridge. For the SMART1500LCDXL model, only Tripp Lite BP24V15RT2U external battery pack (rated 24Vdc, 14Ahr with overcurrent protection) should be connected to the external battery pack connector. For further information about replacement compatibility and ordering, visit Tripp Lite on the Web at http://www.tripplite.com/products/battery-finder/
To Replace the Batteries:
To avoid battery drain, all connected equipment should be turned off and disconnected from the UPS. Press and hold the button for 2.5 seconds. Your UPS will be completely turned off (deactivated), and will be ready for storage. If you plan on storing your UPS for an extended period, fully recharge the UPS batteries every three months. Plug the UPS into a live AC outlet, turn it on by pressing and holding the button for 2 seconds, and allow the batteries to recharge for 4 to 6 hours. If you leave your UPS batteries discharged for a long period of time, they will suffer a permanent loss of capacity.
A variety of Extended Warranty and On-Site Service Programs are available from Tripp Lite. For more information on service, visit www.tripplite.com/support. Before returning your product for service, follow these steps:
Visit www.tripplite.com/warranty today to register your new Tripp Lite product. You'll be automatically entered into a drawing for a chance to win a FREE Tripp Lite product! *
* No purchase necessary. Void where prohibited. Some restrictions apply. See website for details.
If your Modem/Fax Protection causes harm to the telephone network, the telephone company may temporarily discontinue your service. If possible, they will notify you in advance. If advance notice isn't practical, you will be notified as soon as possible. You will be advised of your right to file a complaint with the FCC. Your telephone company may make changes in its facilities, equipment, operations or procedures that could affect the proper operation of your equipment. If it does, you will be given advance notice to give you an opportunity to maintain uninterrupted service. If you experience trouble with this equipment's Modem/Fax Protection, please visit www. tripplite.com/support for repair/warranty information. The telephone company may ask you to disconnect this equipment from the network until the problem has been corrected or you are sure the equipment is not malfunctioning. There are no repairs that can be made by the customer to the Modem/Fax Protection. This equipment may not be used on coin service provided by the telephone company. Connection to party lines is subject to state tariffs. (Contact your state public utility commission or corporation commission for information.)
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
Note: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
Any changes or modifications to this equipment not expressly approved by Tripp Lite could void the user's authority to operate this equipment.
NOTICE: The Industry Canada label identifies certified equipment. This certification means that the equipment meets the telecommunications network protective, operational and safety requirements as prescribed in the appropriate Terminal Equipment Technical Requirements Document(s). The Department does not guarantee the equipment will operate to the user's satisfaction.
Before installing this equipment, users should ensure that it is permissible to be connected to the facilities of the local telecommunications company. The equipment must also be installed using an acceptable method of connection. The customer should be aware that the compliance with the above conditions might not prevent degradation of service in some situations.
Repairs to certified equipment should be coordinated by a representative designated by the supplier. Any repairs or alterations made by the user to this equipment, or equipment malfunctions, may give the telecommunications company cause to request the user to disconnect the equipment.
Users should ensure for their own protection that the electrical ground connections of the power utility, telephone lines and internal metallic water pipe system, if present, are connected together. This precaution may be particularly important in rural areas.
Users should not attempt to make connections themselves, but should contact the appropriate electric inspection authority, or electrician, as appropriate.
Not compatible with PoE (Power over Ethernet) applications.
For the purpose of regulatory compliance certifications and identification, your Tripp Lite product has been assigned a unique series number. The series number can be found on the product nameplate label, along with all required approval markings and information. When requesting compliance information for this product, always refer to the series number. The series number should not be confused with the marketing name or model number of the product.
Tripp Lite has a policy of continuous improvement. Product specifications are subject to change without notice.
Note on Labeling
Two symbols are used on the label.
V~: AC Voltage
V⎓: DC Voltage
1111 W. 35th Street, Chicago, IL 60609 USA • www.tripplite.com/support
Copyright © 2017 Tripp Lite. All rights reserved.