Technical specifications
EN
Fan-and-filter unit
RAL 7035
Fan-and-filter unit
RAL 9005
EMC fan-and-filter unit
RAL 7035
Rated operating voltage
Rated current max.
Power consumption
Pre-fuse T
Dimensions
Width (B1) x height (H1)
Required mounting cut-
out (B2 x H2)
Depth (T1)
Max. installation depth
(T2)
Air throughput, unimped-
ed airflow with standard
fleece filter mat
Air throughput, unimped-
ed airflow with pleated
filter
Air throughput with outlet
filter, including standard
fleece filter mat
Air throughput with outlet
filter including pleated filter
Outlet filter RAL 7035
Outlet filter RAL 9005
EMC outlet filter
RAL 7035
Fan
Noise pressure level
Operating temperature
Storage temperature
Protection category (to
IEC 60 529)
Tab. 4:
Technical specifications
12
Unit
3239.100
3239.108
3237.600
V
230, 1~,
Hz
50/60
A
0.12/0.11
W
19/18
A
2
mm
204 x 204
mm
177 x 177
mm
24
mm
90
m³/h
100/115
m³/h
110/125
1 x 3239.20x: 74/87
m³/h
2 x 3239.20x: 84/98
1 x 3239.20x: 89/100
m³/h
2 x 3239.20x: 98/112
3239.200
3239.208
3239.060
Axial, shaded pole motor
dB (A)
46/49
°C
-15...+55
°C
-30...+70
IP 54 standard
IP 55 with pleated filter
IP 56 with hose-proof hood
Model No.
3239.110
3239.118
–
115, 1~,
50/60
0.24/0.22
Technical modifications reserved.
Rittal fan-and-filter unit assembly and operating instructions
3239.124
–
–
24 (DC)
0.23
5.5
100
110
Axial, DC motor
46