SANTA FE OASIS™105 Installation & Operation Instructions Our most versatile and energy-efficient Serial Number dehumidifier, the Santa Fe Oasis105, is Install Date perfect for a wide range of applications, Sold By including whole-home, basements, attics, and crawl spaces. It features onboard digital...
Table of Contents Safety Instructions ..................3 Intended Applications ................3 Registrations ....................3 Dehumidifier Set Up .................4 Items Included In Box.................4 Important Precautions ................4 Location Considerations ................4 Installing Leveling Feet ................4 Drain Installation ..................5 Operation ....................6 Controller Instructions ................6 Control Functions ..................6 Modes of Operation ................7 Using Onboard Control ................7 Using Remote / Terminal Control ............7...
• Contact installer or call 1-800-533-7533 for all repair or warranty needs. Intended Application(s) The Santa Fe Oasis105 dehumidifier is intended for use in crawlspaces, basements and whole homes ducted with optional duct kits: however, the unit can be placed in almost any residential setting where dehumidification is desired.
Important Precautions • Do not install the Santa Fe Oasis105 dehumidifier with the intake or exhaust of the unit within 14” of a wall or other obstruction. Avoid directing the discharge air at people. The dehumidifier should be used in the upright position •...
Improper installation of the drain hose may result in water leakage. If the Santa Fe Oasis105 dehumidifier is located too far from the floor drain and the provided hose does not reach, you may use a 1/2”...
Changes fan modes from Low (Lo), Auto(Au) and High (HI) press and hold button for High override. Terminal block Used to wire in external signals when in Terminal Control Mode Santa Fe Oasis105 Installation & Operation Instructions Santa-Fe-Products.com | 800.533.7533...
Input (Use Normally Closed Switch). Alarm: Normally Closed Relay Output - Indicates when dehumidifier is in an alarm state. Alarm: Outputs a 24V signal when the Dehumidifier returns an on board error code. 800.533.7533 | Santa-Fe-Products.com Santa Fe Oasis105 Installation & Operation Instructions...
Air Filtration The Santa Fe Oasis105 dehumidifier is equipped with MERV-13 air filter (89-90% ASHRAE dust spot). The filters should be checked and replaced every three to six months. Operating the unit with a dirty filter will reduce dehumidifier capacity and efficiency.
The Oasis105 is designed to operate between 49 °F and 115 °F. If the inlet air temperature is out of this range, the unit will display an error code and not operate.
Ducting To Finished Areas (Optional) Return and supply duct collars are optional accessories for the Santa Fe Oasis105 and not included with the unit. Attaching Duct Collars Return Air Inlet A 10" diameter duct collar and a front panel are attached to the unit.
Dehumidistat (mounts on Duct Work opposite wall in finished area) • Place the Santa Fe dehumidifier in the unfinished area of the basement, near a drain access (condensate will • Place the Santa Fe dehumidifier in the unfinished area drain via gravity or with an optional pump kit).
Ducting To HVAC Systems Return and supply duct collars are optional accessories for the Santa Fe Oasis105 and not included with the unit. CAUTION! DO NOT CONNECT WITH A STATIC PRESSURE GREATER THAN OR EQUAL TO +1.0 WG. CONTACT TECHNICAL SUPPORT AT (800) 533-7533 FOR ADDITIONAL DETAILS.
• Install a dedicated 10" air return for the Santa Fe Oasis105 from a central area of the structure. • Duct the supply of the Santa Fe Oasis105 to the supply of the HVAC system with a backdraft damper.
Page 14
Installation in a Basement or Crawlspace Install a separate 10" return for the Oasis105 in a central area of the structure. Duct the supply of the dehumidifier to the air supply of the HVAC system with a backdraft damper.
Page 15
Ducting To HVAC Systems 2. Alternative HVAC System Installation If the Recommended Dedicated Oasis105 Return to HVAC Supply Installation is not possible, there are several alternative installation options available. • DO NOT locate return in a bathroom or kitchen. •...
Page 16
(optional). The supply of the Oasis105 Dehumidifier should be ducted to the rooms in the home that have the ductless mini-split heads and as close to the heads as possible. Be sure to utilize multiple rooms to allow air inside the structure to properly circulate.
1. Defective sensor minutes. temperature 2. Loose connection • After the compressor runs sensor for 15 minutes, the unit will go into defrost mode for 30 minutes. • This process will repeat. 800.533.7533 | Santa-Fe-Products.com Santa Fe Oasis105 Installation & Operation Instructions...
Power board will be in when refrigeration in the refrigeration system system protection mode. operating system 2. Incoming air temp is too high below 90°F incoming Santa Fe Oasis105 Installation & Operation Instructions Santa-Fe-Products.com | 800.533.7533...
The unit should not be used in areas prone to flooding. Consult local electrical codes for any further information. An optional remote dehumidistat is available for use with the Santa Fe Oasis105 dehumidifier and is to be located remotely from the dehumidifier.
Warranty Limited Warranty. Therma-Stor, LLC (“Therma-Stor”) warrants as follows: (i) the Santa Fe Oasis105 dehumidifier (“Product”) will be free of material defects in workmanship or materials for a period of 2 years (“Two-Year Warranty”) following the date of initial purchase of such Product by an original customer purchasing from Therma-Stor or an authorized reseller (“Customer”);...
Warranty Registration Card REGISTER YOUR PRODUCT. PART NUMBER SERIAL NUMBER www.thermastor.com/registration Register your product using the serial number and part number above at www.thermastor.com/registration 800.533.7533 | Santa-Fe-Products.com Santa Fe Oasis105 Installation & Operation Instructions...