Advertisement

ULTRA SERIES | ULTRA155/205
Installation & Operation Instructions
The Santa Fe Ultra155/205 Dehumidifiers are
ventilating dehumidifiers that integrate into the
heating and cooling system to provide the ultimate
in comfort, health and property protection through:
+ Dehumidification
+ Fresh Air Ventilation (Optional)
+ Air Filtration
* The Santa Fe Ultra155/205 were previously known as the
Ultra Aire 155H/205H.
800.533.7533 | Santa-Fe-Products.com
Santa-Fe-Products.com | 800.533.7533
Serial Number
Install Date
Sold By
Patent: thermastor.com/patents
Santa Fe ULTRA155/ULTRA205 Installation & Operation Instructions
1
TS-1159 04/21 Rev A

Advertisement

Table of Contents
loading

Summary of Contents for Santa Fe ULTRA Series

  • Page 1 + Dehumidification + Fresh Air Ventilation (Optional) + Air Filtration * The Santa Fe Ultra155/205 were previously known as the Patent: thermastor.com/patents Ultra Aire 155H/205H. 800.533.7533 | Santa-Fe-Products.com Santa Fe ULTRA155/ULTRA205 Installation & Operation Instructions Santa-Fe-Products.com | 800.533.7533...
  • Page 2: Table Of Contents

    Warranty ......................17 FOR REPAIR & TECH SUPPORT: 1-800-533-7533 (follow prompts) or CONTACT US AT: service@madisoniaq.com Santa Fe is committed to manufacturing quality products. To maintain our standards, product specifications may change without notice. 4201 Lien Road, Madison, WI 53704 (800) 533-7533 Thermastor.com | Santa-Fe-Products.com...
  • Page 3: Safety Instructions

    THIS SYMBOL MEANS IMPORTANT INSTRUCTIONS. FAILURE TO HEED THEM CAN RE- SULT IN INJURY OR MATERIAL PROPERTY DAMAGE. Registrations This Santa Fe Dehumidifier conforms to unified standard UL 60335-2-40 and CSA Standard C22.2 No. 92. WARNING! WARNING! 120 VOLTS MAY CAUSE SERIOUS INJURY FROM ELECTRIC SHOCK.
  • Page 4: Dehumidifier Set Up

    • DO NOT place the dehumidifier directly on structural building members without vibration absorbers or unwanted noise may result. Place the Santa Fe Dehumidifier on supports to raise the base of the unit. • A drain pan with a float switch MUST be placed under the dehumidifier if installed above a living area or above an area where water leakage could cause damage.
  • Page 5: Attaching Duct Collars

    Adhere seal onto the back of the oval duct and mount the duct to the front of the dehumidifier using the screws provided. 6" Fresh Air Inlet (Optional) 10" Return Air Inlet 10" Supply Air Outlet Collars and hardware are SIDE VIEW FRONT VIEW located here. 800.533.7533 | Santa-Fe-Products.com Santa Fe ULTRA155/ULTRA205 Installation & Operation Instructions...
  • Page 6: Electrical Requirements

    (9') easily reaches a 115 VAC electrical outlet with a minimum of 15 Amp circuit capacity. The Santa Fe 205H requires a dedicated 20 Amp circuit. If used in an area that may become wet, a GFCI protected circuit is recommended.
  • Page 7: Drain Installation

    1" per 10'. An optional condensate pump kit is available for use with the Santa Fe Dehumidifier and may be installed if lift is required to dispose of condensate. Condensate is automatically pumped to a remote location when the Drain water level in the pump’s reservoir rises to close the float switch.
  • Page 8: Ducting To Hvac Systems

    Duct the supply of the unit to the air supply of the existing HVAC system. Connect an insulated duct from outside to the 6" collar of the Santa Fe Dehumidifier to provide fresh make-up air. Adjust the damper in the duct to provide the desired amount of fresh air.
  • Page 9: Recommended Hvac System Installation

    • Install a dedicated air return for the Santa Fe Dehumidifier from a central area of the structure. • Install an insulated duct from outside to the 6" collar of the Santa Fe Dehumidifier to provide fresh air ventilation (optional).
  • Page 10: Fresh Air Ventilation

    The time and frequency of ventilation should be based on the size and occupancy of the residence. • The fresh air ventilation duct should be connected to the 6" round collar on the front of the Santa Fe De- humidifier.
  • Page 11: Determine Ventilation Requirements

    Number of Bedrooms Floor Area < 500 501 - 1000 1001 - 1500 1501 - 2000 2001 - 2500 2501 - 3000 Table 4.1 from ASHRAE 62.2-2016 Record the required CFM ____________ 800.533.7533 | Santa-Fe-Products.com Santa Fe ULTRA155/ULTRA205 Installation & Operation Instructions...
  • Page 12: Controls

    CONTROLS A control must be used with this Santa Fe Dehumidifier. Santa Fe offers the DEH 3000 proprietary control. The DEH 3000 allows homeowners to monitor and control relative humidity and proper ventilation levels in their home. This control is also available with a remote sensing option.
  • Page 13: Air Filtration

    AIR FILTRATION This Santa Fe Dehumidifier is equipped with a MERV-13 (Dimensions: 1.75” x 15.50” x 19.50”) filter. The filter should be checked and replaced every three to six months. Operating the unit with a dirty filter will reduce dehumidifier capacity and efficiency.
  • Page 14: Merv Rating Chart

    Sanding Dust <20% 65-70% Spray Paint Dust Electrostatic - Self charging Textile Fibers Window A/C Units woven panel filter. <20% <65% Carpet Fibers Table Data Source: United States Environmental Protection Agency Santa Fe ULTRA155/ULTRA205 Installation & Operation Instructions Santa-Fe-Products.com | 800.533.7533...
  • Page 15: Service

    9. If this test works, then the field control wiring flow restricted. is ok. 6. Defective fan or relay. 10. If the problem persists, then the control is most likely faulty. 800.533.7533 | Santa-Fe-Products.com Santa Fe ULTRA155/ULTRA205 Installation & Operation Instructions...
  • Page 16 Refrigerant Charging WARNING! WARNING! SERVICING THE SANTA FE DEHUMIDIFIER WITH ITS HIGH PRESSURE REFRIGERANT SYSTEM AND HIGH VOLTAGE CIRCUITRY PRESENTS A HEALTH HAZARD WHICH COULD RESULT IN DEATH, SERIOUS BODILY INJURY, AND/OR PROPERTY DAMAGE. SERVICE MUST BE PERFORMED BY A QUALIFIED SERVICE TECHNICIAN.
  • Page 17: Warranty

    WARRANTY Limited Warranty. Therma-Stor, LLC (“Therma-Stor”) warrants as follows: (i) the Santa Fe Dehumidifier dehumidifier (“Product”) will be free of material defects in workmanship or materials for a period of two (2) years (“Two-Year Warranty”) following the date of initial purchase of such Product by an original customer purchasing from Therma-Stor or an authorized reseller (“Customer”);...
  • Page 18 Santa-Fe-Products.com 1.800.533.7533...

This manual is also suitable for:

Ultra155Ultra205

Table of Contents