Step 3 - Connect DC Input

Verify that the DC Input voltage is 48VDC using a meter.
Match the marked polarity on all inputs.
Note: Incorrect Input Voltage or Polarity will cause the equipment to not operate properly.
1.
Size input cables to minimize voltage drop for installation (recommended wire size is 12 AWG (2.5 mm
2. Strip 0.35" or 7/20" (9 mm)
3. Tighten the screw -(1/16" flat screw driver). torque to 4.5 in-oz (0.5 Nm)
4. Pull wire to verify connection.
Caution: Ensure cables do not come in contact with sharp or rough surfaces that may damage insulation and cause
a short circuit.
DC Inputs - NEC Class 2
Note
For 2 circuit combiner there are two input connections.
:
Step 4 - Connect DC Output
There are 2 DC terminal Outputs
1. Use appropriately sized output cable for the load being served.
2. Strip the output wire 1/2".
3. Insert wire fully into wire entry.
4.
5. Pull wire to verify insertion.