FX-PCX47 Expansion Input/Output Module Installation
Instructions
FX-PCX4711-x
Application
The FX-PCX47 controller is part of the Facility Explorer
FX-PC Series Programmable Controller family. FX-PCX
controllers expand the number of points connected to an
FX-PCA, FX-PCG, or FX-PCV programmable controller
or to a supervisory controller.
FX-PCX47 controllers operate on an RS-485 BACnet®
Master-Slave/Token-Passing (MS/TP) Bus as BACnet
Application Specific Controllers (B-ASCs) and integrate
into Johnson Controls® and third-party BACnet systems.
Note: At FX-PCT Release 10.1, a new capability was
introduced allowing FX-PCVs, FX-PCGs, and
FX-PCAs to communicate by using either the
BACnet or the N2 field bus networking protocol.
The operation of the FX-PCX Input/Output Module
is not affected by the selection of the BACnet or
the N2 protocol in the host controller.
North American Emissions
Compliance
Canada
This Class (A) digital apparatus meets all the
requirements of the Canadian Interference-Causing
Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte toutes
les exigences du Règlement sur le matériel brouilleur
du Canada.
United States
This equipment has been tested and found to comply
with the limits for a Class A digital device pursuant to
Part 15 of the FCC Rules. These limits are designed to
provide reasonable protection against harmful
interference when this equipment is operated in a
commercial environment. This equipment generates,
uses, and can radiate radio frequency energy and, if not
installed and used in accordance with the instruction
manual, may cause harmful interference to radio
communications. Operation of this equipment in a
residential area may cause harmful interference, in which
case the users will be required to correct the interference
at their own expense.
FX-PCX47 Expansion Input/Output Module Installation Instructions
Part No. 24-10144-122, Rev. E
Refer to the
QuickLIT website
Installation
Observe these guidelines when installing a controller:
Transport the controller in the original container to
minimize vibration and shock damage.
Verify that all parts shipped with the controller.
Do not drop the controller or subject it to physical
shock.
Parts Included
one controller with removable terminal blocks (Power
and SA/FC bus are removable)
one installation instructions sheet
Materials and Special Tools Needed
three fasteners appropriate for the mounting surface
(M4 screws or #8 screws)
one 20 cm (8 in.) or longer piece of 35 mm DIN rail
and appropriate hardware for DIN rail mount (only)
small straight-blade screwdriver for securing wires in
the terminal blocks
Mounting
Observe these guidelines when mounting a controller:
Ensure the mounting surface can support the
controller, DIN rail, and any user-supplied enclosure.
Mount the controller horizontally on 35 mm DIN rail
whenever possible.
Mount the controller in the proper mounting position
(Figure
1).
Mount the controller on a hard, even surface
whenever possible in wall-mount applications.
Use shims or washers to mount the controller securely
and evenly on the mounting surface.
Mount the controller in an area free of corrosive
vapors and observe the Ambient Conditions
requirements in
Table
10.
Provide for sufficient space around the controller for
cable and wire connections for easy cover removal
and good ventilation through the controller (50 mm
[2 in.] minimum on the top, bottom, and front of the
controller).
Issued April 2016
for the most up-to-date version of this document.
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the FX-PCX47 and is the answer not in the manual?

Questions and answers

Summary of Contents for Johnson Controls FX-PCX47

  • Page 1 Application Installation The FX-PCX47 controller is part of the Facility Explorer FX-PC Series Programmable Controller family. FX-PCX Observe these guidelines when installing a controller: controllers expand the number of points connected to an •...
  • Page 2: Wall Mount Applications

    Mounting the controller horizontal on 35 mm DIN rail is the preferred mounting method. To mount an FX-PCX47 controller on 35 mm DIN rail: 1. Securely mount a 20 cm (8 in.) or longer section of 35 mm DIN rail horizontal and centered in the desired...
  • Page 3 Figure 3: FX-PCX47 Physical Features Table 1: FX-PCX47 Physical Features Callouts and Descriptions Callout Physical Feature Description Binary Output (BO) Source Power Selection Jumper Pin Blocks, 3 – BO Jumper Pin Blocks. (See Table Device Address DIP Switch Block. (See...
  • Page 4: Input And Output Terminal Blocks

    Bulletin (LIT-12011670) or MS/TP Communications Bus for BCM System Technical Bulletin (LIT-12011908). Terminal Blocks and Bus Ports Figure 3 for terminal block and bus port locations on the controller. Observe the following guidelines when wiring a controller. FX-PCX47 Expansion Input/Output Module Installation Instructions...
  • Page 5: Supply Power Terminal Block

    The controller can also be installed in a wireless application using an FX-ZFR1811 Wireless Field Bus Router. To configure a controller for use with the FX-ZFR Series Wireless Field Bus system: Note: FX-PCXs can talk wirelessly on the FC bus only. FX-PCX47 Expansion Input/Output Module Installation Instructions...
  • Page 6: Termination Details

    Addresses. (Part No. 24-10325-29). Termination Details A set of Johnson Controls® termination diagrams provides details for wiring inputs and outputs to the controllers. See the figures in this section for the applicable termination diagrams. Table 2: Termination Details Type of Field Device...
  • Page 7 Current Input - Internal Source (3 wire) Current Input - External Source (in Loop) Feedback from EPP-1000 Dry Contact (Binary Input) UI or BI 0–20 VDC Output to Actuator CO or AO (External Source) FX-PCX47 Expansion Input/Output Module Installation Instructions...
  • Page 8 CO or AO (Internal Source) 4–20 mA Output to Actuator CO or AO 4–20 mA Output to Actuator CO or AO Voltage (Analog Output) Analog Output (Current) 24 VAC Triac Output (Switch Low, External Source) FX-PCX47 Expansion Input/Output Module Installation Instructions...
  • Page 9 High, Externally Sourced) Incremental Control to Actuator (Switch High, Externally Sourced) Incremental Control to Actuator (Switch Low, Externally Sourced) 24 VAC Binary Output (Switch Low, Externally Sourced) 24 VAC Binary Output (Switch High, Externally Sourced) FX-PCX47 Expansion Input/Output Module Installation Instructions...
  • Page 10 Incremental Control to Actuator (Switch High, Externally Sourced) Network Stat with Phone Jack SA Bus (Fixed Address = 199) Network Stat with Terminals SA Bus Addressable Network Stat with Terminals SA Bus (Fixed Address = 199) FX-PCX47 Expansion Input/Output Module Installation Instructions...
  • Page 11: Terminal Wiring Guidelines, Functions, Ratings, And Requirements

    Cable runs over 30 m (100 ft) may require an offset in the input/output software setup. Table 3: FX-PCX47 Terminal Blocks, Functions, Ratings, Requirements, and Cables Terminal Block Terminal Function, Ratings, Requirements...
  • Page 12 Table 3: FX-PCX47 Terminal Blocks, Functions, Ratings, Requirements, and Cables Terminal Block Terminal Function, Ratings, Requirements Determine Wire Size and Label Label Maximum Cable Length BINARY Binary Input - Dry Contact Maintained Mode See Guideline A in Table (Inputs) 0.01 second minimum pulse width Internal 18 V.
  • Page 13 Table 3: FX-PCX47 Terminal Blocks, Functions, Ratings, Requirements, and Cables Terminal Block Terminal Function, Ratings, Requirements Determine Wire Size and Label Label Maximum Cable Length BINARY OUTn Binary Output - 24 VAC Triac (Internal Power Source) See Guideline C in...
  • Page 14: Cable And Wire Length Guidelines

    (in mA) when wiring inputs and outputs. Figure 8: Maximum Wire Length for Low-Voltage (<30V) Inputs and Outputs by Current and Wire Size FX-PCX47 Expansion Input/Output Module Installation Instructions...
  • Page 15: Sa/Fc Bus And Supply Power Wiring Guidelines

    The SA Bus and FC Bus wiring recommendations in this table are for MS/TP bus communications at 38,400 baud. For more information, refer to the FX-PC Series Controllers MS/TP Communications Bus Technical Bulletin (LIT-12011670) or MS/TP Communications Bus for BCM System Technical Bulletin (LIT-12011908). FX-PCX47 Expansion Input/Output Module Installation Instructions...
  • Page 16: Setup And Adjustments

    21, set switch 16 to ON that are hardwired to an SA Bus or FC Bus. (Switch first, then set switch 4 ON, followed by switch 1 128 Off) (16+4+1= 21). See Figure FX-PCX47 Expansion Input/Output Module Installation Instructions...
  • Page 17: Removing The Controller Cover

    Figure 10: FX-PCX47 with Cover Removed Showing EOL Switch and Jumper Positions Table 6: SA/FC Bus Device Address Descriptions Device Use on Description Address 0 to 3 Reserved addresses for wired slave devices (not for use on controllers). (Switch 128 ON)
  • Page 18: Input/Output Jumper Settings

    UI on the FX-PCX47 controller. of the BOs terminal block. Table 7: FX-PCX47 UI Inputs and Jumper Labels Figure 12: Example Binary Outputs and the Universal Input Jumper Label on Circuit Board...
  • Page 19: Troubleshooting The Controllers

    AP-TBK4FC-0 Replacement FC Bus Terminal Blocks, 4-Position, Blue, Bulk Pack of 10 Note: These terminal blocks can be used as replacement parts if keeping consistent terminal block colors is important. FX-PCX47 Expansion Input/Output Module Installation Instructions...
  • Page 20 Note: The ZFR-USBHA-0 replaces the IA OEM DAUBI_2400 ZigBee USB dongle. For additional information on the ZFR-USBHA-0 ZigBee dongle, refer to the FX-ZFR Series Wireless Field Bus System Technical Bulletin (LIT-12011660) or FX-ZFR Series Wireless Field Bus System Quick Reference Guide (LIT-12011696). FX-PCX47 Expansion Input/Output Module Installation Instructions...
  • Page 21: Technical Specifications

    150 x 190 x 53 mm (5-7/8 x 7-1/2 x 2-1/8 in.) including terminals and mounting clips Note: Mounting space requires an additional 50 mm (2 in.) space on top, bottom and front face of controller for easy cover removal, ventilation and wire terminations. Weight 0.5 kg (1.1 lb) FX-PCX47 Expansion Input/Output Module Installation Instructions...
  • Page 22 The performance specifications are nominal and conform to acceptable industry standard. For application at conditions beyond these specifications, consult the local Johnson Controls® office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.

Table of Contents