7. Sequence Chart of Control Signals
In order to avoid some fault operations and deviations, PUL, DIR and ENA should abide by some rules,
shown as following diagram:
Remark:
a)
t1: ENA must be ahead of DIR by at least 200ms. Usually, ENA+ and ENA- are NC (not connected).
See "Connector P1 Configurations" for more information.
b)
t2: DIR must be ahead of PUL effective edge by 2us to ensure correct direction;
c)
t3: Pulse width not less than 1us;
d)
t4: Low level width not less than 1us;
e)
Duty cycle of PUL signal is recommended 50%.
Figure 7:Brake output connection
Figure 8: Sequence chart of control signals
8
CL86T(V4.0) Closed Loop Stepper Drive User Manual