Power Supply "24Vdc", (X1); Operative Earth (X11) - Kendrion Vico MT 727 User Manual

Multi-touch panel with codesys hmi web terminal
Table of Contents

Advertisement

Kendrion Kuhnke Automation GmbH

Power Supply "24VDC", (X1)

On-board power supply unit (PSU)
The device is designed for an input voltage of 24 VDC (+20% /- 20%). It is protected against reverse polarity.
Both the cord to the device and the power supply unit must have external protection against short circuit and
overload triggering at max. 10 A.
The unit's earth connector dissipates disturbances caused by external signal cables or cables of other
assemblies. You should therefore use the operative earth connector of power supply connector X1 to provide
a low-impedance earth connection. We recommend using 1.5 mm² diameter wires.
Pin wiring:
Connection data

Operative Earth (X11)

Information
A low-impedance earth conductor improves the dissipation of interference received via external
power supply cables, signal cables or cables of peripheral units.
Vico MT (E 863 GB)
01/10/2021
X9
24 VDC Power Supply
Pin / Signal
1
OE
2
0 V
3 /
24V
X9
Mating Connector
Type
Poles
Order data
Wire cross section
Stripped end:
Connect operative earth to the protective earth conductor of the switching
cabinet or the system that the PC is installed in. Use the flat plug (6.3 mm x
0.8 mm) or the earth bolt at the back of the unit.
Verify that the cross section is not less than 1.5 mm
the cabinet terminal as short as possible.
Construction and Functionality
Function
operative earth
external 0 V power supply
external power supply
24 VDC (18 V ... 32 V)
screwed connection with spring bushing
2, single row
Phoenix FKCN 2.5/ 3-ST– 1732755
(included in package)
2
flexible 0.2 mm
... 2.5 mm
2
rigid
0.2 mm
... 1.5 mm
AWG / kcmil: 24 ... 16
10 mm
2
2
2
. Try to keep the lead to
22

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vico mt 1027Vico mt 1527