Timing
Closing time: ±1 s
Opening time: ±1 s from start of flow till outlet pressure
is 1 mbar.
Enclosure
IP 40: when used with covers or plugs
IP 44: when used with DIN plugs according to DIN 43650
Valve classification
st
1
valve; class B
nd
2
valve; class C
Mounting holes
Two M5 mounting holes are located on the bottom of the gas
control.
The four holes at inlet and outlet side for mounting the flange
to the gas control are provided with M5 thread with
min. 6.5 mm full thread.
36
36
A -- Cap screw/offset adjustment screw
B -- 6.3 AMP terminals
C -- Inlet pressure tap
D --Throttle adjustment screw
E -- Outlet pressure tap
F -- Pilot outlet connection
G -- M5 air pressure connection
EN1R- -9170 0109R1- -NE
31
B
58
21
29
25
115
J
1
L
/
d
2
*
d
M
36
N
5.5
Fig. 1. Adjustment points and dimensions
Electrical data
Power consumption at 220/240 V
st
1
operator: 3.6/4.7 W
nd
2
operator: 3.4/4.5 W
Current at 220/240 V
st
1
operator: 32/36 mA
nd
2
operator: 20.4/24 mA
75
A
22 24
C
D
E
92
G
21
127
H -- Terminals according to DIN 43650
J -- Inlet
K -- Outlet
L -- M5 mounting holes for mounting the flange
M -- M5 mounting holes for mounting the gas control
N -- Surface to be clamped
2
64
F
H
118
F
K
69
36
L
* d = 30 --
* d = 36 --
37
36
1
/
" ISO 7--1
2
3
/
" ISO 7--1
4

Advertisement