Tyco MX Technology 801Ex Series Information Sheet

Tyco MX Technology 801Ex Series Information Sheet

Intrinsically safe analogue addressable detectors

Advertisement

DESCRIPTION

801PHEx Photoelectric/Heat
801CHEx CO/Heat
CP840Ex Manual Call Point
The 801Ex range of Intrinsically Safe MX analogue fire
detectors and callpoints are rated for installation in certain
hazardous areas. They transmit digital values to compatible
MX Control and Indicating Equipment (c.i.e.) to indicate the
level of smoke/CO/heat/flame they are sensing. The c.i.e.
determines the condition, alarm, fault, etc, and responds
according to the detection mode selected in the site
configuration.
By using dual sensors in the 801PHEx and 801CHEx a wider
range of fire risks can be covered. The 801FEx is a single
wavelength infrared flame detector that has an optical filter
to reduce the effects of sun and artificial lighting. It has a
range of up to 18m with a field view of 1100m
N-heptane pan fire. The CP840Ex is an I.S. manual call point
and in addition the IF800 I.S. Input Module is available for
interfacing to a clean contact device within the hazardous
areas. For use in hazardous areas the standard MX loop
voltage must be reduced and isolated. This is achieved by
using an EXI800 I.S. Interface Module and a P&F KFDO-CS-
Ex1.54 Isolator to connect each spur of MX I.S. devices onto
the MX Loop.

SPECIFICATIONS

(less base)
Height
Diameter
Weight
Loop Voltage
Quiescent Current (typical) 350µA
Alarm Current
Max. Detectors per Loop
1
Ambient Temperature
2
Storage Temperature
Relative Humidity
3
IECEx Certificate
Standards
Part Number
1. MX c.i.e. Refer to appropriate manual LT0360 (MX1-NZ) LT0441 (MX1-Au) for design specifications.
2. Maximum ambient temperature depends on temperature threshold set for heat detector.
3. Maximum, non condensing.
801EXxxinf0906 Issue 1
801HEx Heat
801FEx Flame
for a 0.4m
2
801PHEx
801CHEx
Photoelectric/Heat CO/Heat
43mm
43mm
108mm
108mm
126g
126g
18V to 24Vdc addressable loop voltage is provided by the EXI800
300µA
3mA
3mA
250
250
–25°C to +70°C
0 to +55°C
–40°C to +80°C
–20°C to +55°C
95%
95%
BAS 07.0063X
BAS 07.0063X
EN54-5
EN54-5
EN54-7
516.800.530
516.800.531
©Tyco Safety Products - Fire Detection - ANZ Region
MX TECHNOLOGY
Analogue Addressable Detectors
I N F O R M A T I O N S H E E T
2
There are limits to the IS spur loading and MX loop design so
refer to the relevant MX c.i.e design manuals.
All detectors must be used with the 5BEx base in hazardous
areas.
801FEx
Flame
43mm
108mm
110g
300µA
3mA
250
–20°C to +70°C
–40°C to +80°C
90%
BAS 07.0075X
EN54-10
516.800.066
Tyco 801Ex Series
Intrinsically Safe
801HEx
CP840Ex
Heat
Call Point
43mm
59mm
108mm
124mm
120g
340g
280µA
250µA
3mA
4.5mA
250
250
–25°C to +70°C
–25°C to +70°C
–40°C to +80°C
–40°C to +70°C
95%
95%
BAS 07.0063X
BAS 07.0063X
EN54-5
EN54-11
516.800.532
514.800.513
29 June 2009
Page 1 of 2

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the MX Technology 801Ex Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Tyco MX Technology 801Ex Series

  • Page 1 1. MX c.i.e. Refer to appropriate manual LT0360 (MX1-NZ) LT0441 (MX1-Au) for design specifications. 2. Maximum ambient temperature depends on temperature threshold set for heat detector. 3. Maximum, non condensing. 29 June 2009 801EXxxinf0906 Issue 1 ©Tyco Safety Products - Fire Detection - ANZ Region Page 1 of 2...
  • Page 2 MAINTENANCE AND SERVICE be used. Typical heat detector applications are satisfied by the use of The Tyco MX addressable system should be maintained in accordance rate-of-rise and fixed temperature electronic detectors. The addition with AS 1851/NZS 4512. The Tyco X300 Smoke Tester, X461 of rate-of-rise operation provides faster heat detection for use where Heat Tester and CO Test Gas (part no.